EN 

 
 

DESCRIPTION 

As standard, the Scala Plus is suitable for panel/wall installations, flush or surface mounting, either in a horizontal 
or vertical plane. 100mm ducting (flexible or straight) can be attached using the supplied adjustable spigot, 
providing rear or side exit options. For wall installations a Wall Kit (8000000002 White) can be used. An optional 
filter is also available (8000000018).  
 

A. INSTALLATION 

 

PANEL MOUNTING (Surface)

 

1.  Cut a 105mm

 hole through the panel, ensuring that there is sufficient space for the product to be installed 

and that the filter can be removed for maintenance. 

2.  Removing the grille, Firstly remove the front cover by carefully pulling each corner of the front panel until it is 

free to be removed from the inner grille (Fig 1). Unscrew the two screws at the bottom of the inner grille. The 
screws will remain in the inner grille but will be loose when the grille is ready to be removed (Fig 1).

 

Lift the 

inner grille from the bottom. 

3.  Remove the Spigot Ring from inside the carton and clip over the Spigot Adaptor making sure the lip on the 

Spigot Ring locates firmly inside the groove on the Spigot Adaptor (Fig 2). Ensure that the Spigot Adaptor is 
firmly located onto the Base Housing and the shutter is still securely fastened and fully functional. 

4.  Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP. 

 

5.  Attach the ducting to the Spigot and locate into the hole in the panel ensuring the Skirt is located correctly into 

the Base Housing. Secure into position using appropriate fixtures (Fig 3). 

6.  Ensure the Impeller rotates freely. 
7.  Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

8.  Replace the inner grille. Replace the front panel.

 

 

9.  Switch the mains power supply on and check the fan is operating correctly. 

 

PANEL MOUNTING (Flush)

 

1.  Mark and cut a rectangular hole (190mm x 240mm) through the panel, ensuring that there is sufficient space 

for the product to be installed and that the filter (If fitted) can be removed for maintenance. IMPORTANT: Be 
careful to avoid joists and hidden cables.  

2.  Removing the grille, Firstly remove the front cover by carefully pulling each corner of the front panel until it is 

free to be removed from the inner grille (Fig 1). Unscrew the two screws at the bottom of the inner grille. The 
screws will remain in the inner grille but will be loose when the grille is ready to be removed (Fig 1).

 

Lift the 

inner grille from the bottom edge. 

3.  Remove the Spigot Ring from inside the carton and clip over the Spigot Adaptor, making sure the lip on the 

Spigot Ring locates firmly inside the groove on the Spigot Adaptor (Fig 2). The Spigot can be repositioned for 
side exit installations by removing the screw and sliding the spigot away from the rear of the Base Housing, 
carefully observing the guide rails (Fig 4). The Spigot can then be rotated and repositioned for side exit using 
the same guide rails and retaining screw (Fig 4)

.

 Ensure that the Spigot Adaptor is firmly located onto the 

Base Housing in the required orientation and the shutter is still securely fastened and fully functional. 

4.  Remove the Skirt and pass the supplied screw fully through the flange of the base housing. Then attach the 3 

supplied Panel Clips (Fig 5) and partially screw into place until they are properly retained (allowing enough 
gap for the panel thickness). 

 

 

5.  Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP.

 

6.  Attach the ducting to the Spigot and locate into the hole in the panel, ensuring the cable is fed into the Base 

Housing and the Panel Clips spring out behind the panel.  

7.  Secure into position by carefully tightening the Panel Clips. It may be necessary to hold the product centrally 

in the hole while tightening so that no gaps are seen once the cover is on. 

IMPORTANT: If power tools are 

used, set them to the minimum torque setting or preferably use a manual screwdriver. Do not over 
tighten.

  

8.  Ensure the Impeller rotates freely. 
9.  Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

10.  Replace the inner

Replace the front panel.

 

 

11.  Switch the mains power supply on and check the fan is operating correctly. 
 
 

WALL MOUNTING (Surface) 

For wall installations a Wall Kit (8000000002 White) can be used.

 

1.  Cut a 115mm. 

 hole through the wall, ensuring that there is sufficient space for the product to be installed 

and that the filter (if fitted) can be removed for maintenance.  

2.  Insert the wall sleeve with the smaller diameter sleeve on the room-side and cement both ends into position 

flush with the wall faces. The wall sleeve should be angled downwards, away from the fan, to allow any 
condensation to drain to the outside wall. 

3.  Outside Grille: Using the Back Plate as a template, mark the fixing hole centres on the wall. Drill and plug the 

wall and fix the Back Plate into position.  

4.  Fix the Outside Grille on to the Back Plate (screws provided). Ensure the louvres are pointing downwards. 

Summary of Contents for Lo-Carbon Scala Plus HT

Page 1: ...de c blage FR Installations und Verdrahtungsanweisungen DE Montage en bekabelingsinstructies NL PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS VEUILLEZ LIRE...

Page 2: ...ith the rating label D The Fan should only be used in conjunction with the appropriate Vent Axia products E It is recommended that the connection to the fan connector terminals is made with flexible c...

Page 3: ...he grille is ready to be removed Fig 1 Lift the inner grille from the bottom edge 3 Remove the Spigot Ring from inside the carton and clip over the Spigot Adaptor making sure the lip on the Spigot Rin...

Page 4: ...led This will determine the speed at which the fan will run continuously if the constant trickle speed option is enabled 1 above Low trickle speed Switch dip switch 1 into the OFF position Fig 6 High...

Page 5: ...d cable clamps are securely fastened 4 Ensure the impeller rotates and is free from obstructions D SERVICING AND MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE P...

Page 6: ...ase soit conforme aux donn es de la plaque signal tique D Le ventilateur ne doit tre utilis qu avec les produits Vent Axia qui conviennent E Nous pr conisons le recours des c bles souples pour le racc...

Page 7: ...cessaires pour viter les solives et c bles cach s 2 Pour retirer la grille commencez pas retirer le capot avant en tirant doucement sur chaque coin de la fa ade jusqu ce qu il puisse tre retir de la g...

Page 8: ...sur le mur Calez le bo tier du ventilateur l emplacement voulu l aide des vis et fixations fournies en veillant ce que la jupe soit correctement centr e sur le bo tier du ventilateur Fig 3 9 V rifiez...

Page 9: ...Autrement dit le ventilateur se d clenche un taux HR plus lev Fig 6 C C BLAGE AVERTISSEMENT LE VENTILATEUR ET L QUIPEMENT DE COMMANDE AUXILIAIRE DOIVENT TRE ISOL S DE L ALIMENTATION SECTEUR PENDANT L...

Page 10: ...s entsprechenden Typenschilds bereinstimmt D Der L fter sollte nur in Verbindung mit den entsprechenden Produkten von Vent Axia eingesetzt werden E Es wird empfohlen eine Verbindung zu den Anschlusskl...

Page 11: ...den kann WICHTIG Achten Sie darauf Balken sowie versteckte Kabel zu vermeiden 2 Um das Gitter zu entfernen entfernen Sie zuerst die Frontabdeckung indem Sie vorsichtig an allen Ecken der Frontabdeckun...

Page 12: ...Sie die Befestigungsl cher an der Wand indem Sie den Geh useboden als Vorlage verwenden und der Luftstutzen vorsichtig in die Mauerh lse eingef hrt wird Befestigen Sie den Geh useboden mithilfe der be...

Page 13: ...Drehen Sie den Feuchteregler H im UHRZEIGERSINN um den Sollwert zu ERH HEN Dadurch reagiert der L fter weniger empfindlich auf Ver nderungen der Luftfeuchtigkeit d h der L fter schaltet sich bei h her...

Page 14: ...alleen samen met geschikte Vent Axia producten worden gebruikt E Gebruik van flexibele kabel voor het verbinden van de contactpunten van de ventilator F Wanneer de ventilator wordt gebruikt om lucht u...

Page 15: ...e onderkant van het binnenste rooster los De schroeven blijven in het binnenste rooster zitten maar zitten los wanneer het rooster moet worden verwijderd fig 1 Til het binnenste rooster aan de onderst...

Page 16: ...INSTELLING WAARSCHUWING DE VENTILATOR EN ONDERSTEUNENDE CONTROLEAPPARATUUR MOET GE SOLEERD WORDEN VAN DE STROOMVOORZIENING TIJDENS DE INSTALLATIE OF HET ONDERHOUD 1 SELECTEER DE OPTIE CONTINUSNELHEID...

Page 17: ...t kan nodig zijn de voedingskabel tussen de buitenkant van de basisbehuizing en de ommanteling door te leiden om te voorkomen dat deze bekneld raakt 3 Controleer of alle verbindingen juist zijn aanges...

Page 18: ...hole locations Emplacements des trous des vis de montage en surface Oberfl chenmontage Position der Schraubenl cher Opbouwmontage plaatsing schroefgaten Fig 4 Converting outlet spigot for side exit a...

Page 19: ...gler Modell HT Verstelinrichting luchtvochtigheid HT model H L N LS Top view of PCB cover showing pot locations and dip switch location Vue du dessus du cache de la carte lectronique illustrant l empl...

Page 20: ...ventilateur suit sa s quence d initialisation Sur les mod les HT le ventilateur s allume et s teint pendant cette s quence LED incluse Apr s cette s quence soit apr s environ deux minutes le ventilate...

Page 21: ...21 Fig 8 T HT wiring diagram Sch ma de c blage T HT T HT Schaltplan T HT aansluitschema...

Page 22: ...orrect electricity supply voltage is shown on the product rating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not autho...

Reviews: