where:
[probe] INT is you want to use the internal probe, EXT for an external probe
[threshold] temperature limit value
[hysteresis] value used to calculate the alarm return threshold. It is subtracted
from the threshold in the case of a maximum alarm, and added to
the threshold in the case of a minimum alarm
[delay] numerical value that indicates after how many minutes of permanence
beyond threshold [threshold] the alarm must be considered
IMPOSTA
ALLARME
MASSIMA restores the current configuration for the
maximum threshold
IMPOSTA
ALLARME
MINIMA restores the current configuration for the minimum
threshold
Some
examples:
IMPOSTA ALLARME MINIMA INT 12 2 30 generates a minimum alarm if the
temperature measured by the internal
probe goes below 12°C for at least 30
minutes and considers the alarm restored
when the temperature exceeds 14°C
(12+2).
IMPOSTA
ALLARME
MASSIMA
EXT
28.5 1.5 50 generates a maximum alarm if
the temperature measured by the
external probe exceeds 28.5°C for
at least 50 minutes and considers
the alarm restored when the
temperature goes below 27°C
(28.5-1.5).
Note: the alarm return is immediate when the alarm return temperature is
reached (no delay)
Power supply failure alarm
In the case of a power supply failure, the Mithos GSM has a buffer battery that
permits operation of the programmable thermostat for approx. one hour.
The recipients of this alarm will receive the following message in the case of power
network failure and restoration:
ALLARME ALIMENTAZIONE=INTERROTTA (gg/mm/aa hh:mm)