Technical data
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
8.6. Motor winder
Rated AC voltage (V)
Power consumption (V•A)
Motor fuse (A)
max winding time
at rated voltage (s)
110
80
1.60
S21 1K
12
230
80
0.75
12
Rated DC voltage (V)
Power consumption (W)
Motor fuse (A)
max winding time
at rated voltage (s)
24
80
4.00
S21 2K
12
48
80
3.00
12
60
80
2.00
12
110
80
1.00
12
220
80
0.75
12
Table 8.6.
8.7. Tightening torques
Thread nominal diameter
Screw joints strength class 8.8
Welded stud
M5
6 Nm
-
M6
10 Nm
6 Nm
M8
25 Nm
14.5 Nm
M10
49 Nm
-
M12
86 Nm
-
Table 8.7.
The table values do not apply for tightening torques
specially mentioned in the documents!
8.8. Materials
Metals
Steel, copper, aluminium, zinc
Plastic materials
PA, PE, PC, Q, EP, (PF/MF), BIIR, laminated fabric
Miscellaneous
Aluminium oxide, lubricants, SF6 gas, oils, greases
Table 8.8.
8.9. Auxiliary and operating materials for circuit-breakers
Application
Auxiliary and operating materials
Manufacturer
Bearing point lubrication
Rivolta SKD 4002
Bremer & Leguil GmbH
Am Burgacker 30-42
47051 Duisburg
To refresh
Base oil for Rivolta
Table 8.9.