IG-322-EN version 03; 22/07/2022
37
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Operation
5.2. Padlocking facility
The circuit-breaker panel is fitted with padlocking facilities
as standard (Figure 5.2). The padlocking facility is opened
by pressing the thumb against the locking resistance of the
locking cover in clockwise direction. The padlocking facility
stops in end position by means of an integrated stop, so
that also the adjacent padlocking facility can be opened.
To ensure that switching actions are always fully carried out,
gates are fitted to the switch actuators. These ensure that
the switching lever can only be removed in the relevant end
limit position.
In the description of the switching operations in
chapters 5.3 and 5.4 the padlocking facilities are not
shown, for the purpose of a clearer representation
of switch position indicators and actuating shafts.
1
2
3
1
Gate
2
Padlocking facility
3
Locking cover
Figure 5.2.
5.3. Delivery state of the circuit-breaker panel
When delivered, the circuit-breaker panel is in the following
state:
• Fastener closed (anti-reverse interlock optional).
Figure 5.3.