IG-322-EN version 03; 22/07/2022
48
Operation
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
2.
Switch the circuit-breaker OFF. To do this, press the
pushbutton OFF (0) on the circuit-breaker control panel
Check that the switch panel is electrically isolated using
capacitive voltage detecting system (see Chapter 6.5).
Figure 5.24.
3.
Deactivate the interlock between the circuit-breaker
and the disconnector or earthing switch respectively.
Do this by moving the operating lever from the bottom
left to the top right position ("Figure 5.25.") (see also
Chapter 4.9, “Panel Interlocks”).
37250329
Leistungsschalter schaltbereit
Operation of circuit breaker
Trennschalter und Erder schaltbereit
Operation of disconnector and earthing switch
Verriegelung nur umstellbar, wenn Leistungsschalter
in 0-Stellung!
Interlocking only to be, if circuit breaker in 0 position!
Verriegelung / Interlocking
Figure 5.25.