AC70T Crane Purpose VFD Manual
37
FA.03
Current hardware
protection settings
LED “0” digit: (CBC)
0: Off 1: On
LED “00” digit: OC protection
interference suppression
0: Off
1: First grade interference
suppression
2: Second grade interference
suppression
LED “000” digit: SC protection
First grade interference
suppression
0: Off
1: First grade interference
suppression
2: Second grade interference
suppression
LED “0000” digit: Reserved
0001
〇
0xA03
FA.04
Reserved
0xA04
FA.05
Bus over voltage
hardware protection
0: Off
1: On
1
〇
0xA05
FA.06
Bus over voltage
suppression function
LED “0” digit: Over voltage
suppression control
0: Prohibited
1: Valid in DEC
2: Valid both in ACC/DEC
LED “00” digit: Over-excitation
control
0: Off
1: On
LED “000” digit: Reserved
LED “0000” digit: Reserved
0012
〇
0xA06
FA.07
Bus over voltage
suppression point
110.0
~
150.0%
128.0%
※
0xA07
FA.08
Bus over voltage
suppression gain
0.0
~
500.0%
100.0%
●
0xA08
FA.09
Bus under voltage
suppression function
0: Prohibited
1: Valid
0
〇
0xA09
FA.10
Bus under voltage
suppression point
60.0
~
90.0%
80.0%
※
0xA0A
FA.11
Bus under voltage
suppression gain
0.0
~
500.0%
100.0%
●
0xA0B
FA.12
Bus under voltage
protection point
60.0
~
90.0%
60.0%
※
0xA0C
FA.13
Reserved
0xA0D