74
11 Supplement
VEGAPULS 67 • 4 … 20 mA/HART - four-wire
36532-EN-160224
Connection cable
Four-wire
Sensor version
Configuration, connection cable
Cable length
Standard cable
Special cable
Screened
4 … 20 mA/HART
50 m
●
–
–
Profibus PA, Founda
-
tion Fieldbus
25 m
–
●
●
Integrated clock
Date format
Day.Month.Year
Time format
12 h/24 h
Time zone Ex factory
CET
Rate deviation max.
10.5 min/year
Additional output parameter - Electronics temperature
Output of the temperature values
Ʋ
Analogue
Via the additional current output
Ʋ
Digital
Depending on the electronics version via the HART,
Profibus PA, Foundation Fieldbus or Modbus signal
Range
-40 … +85 °C (-40 … +185 °F)
Resolution
< 0.1 K
Accuracy
±3 K
Voltage supply
Operating voltage
Ʋ
Version for low voltage
9.6 … 48 V DC, 20 … 42 V AC, 50/60 Hz
Ʋ
Version for mains voltage
90 … 253 V AC, 50/60 Hz
Reverse voltage protection
Integrated
Max. power consumption
4 VA; 2.1 W
Electrical protective measures
Protection rating
IP 66/IP 67 (NEMA 4X)
Overvoltage category (IEC 61010-1)
Ʋ
Version with low voltage
das speisende Netzteil kann an Netze der Überspan
-
nungskategorie III angeschlossen werden
Overvoltage category (IEC 61010-1) - Version with mains voltage
Ʋ
up to 2000 m (6562 ft) above sea level III
Ʋ
up to 5000 m (16404 ft) above sea
level
III - Only with connected overvoltage protection
Ʋ
up to 5000 m (16404 ft) above sea
level
II
Degree of soiling
3
Protection rating (IEC 61010-1)
I