6 Set up with the display and adjustment module
VEGAPULS 67 • 4 … 20 mA/HART - four-wire
36532-EN-160224
Menu
Menu item
Default value
Display
Language
Like order
Displayed value
Distance
Display unit
m
Scaling size
Volume
l
Scaling
0.00 lin %, 0 l
100.00 lin %, 100 l
Backlight
Switched on
Additional adjust-
ments
Distance unit
m
Temperature unit °C
Probe length
Length of the standpipe Ex factory
Linearisation
curve
Linear
HART mode
Standard
Address 0
The sensor offers the HART modes standard and Multidrop. In this
menu item you determine the HART modes and enter the address
with Multidrop.
The mode standard with the fixed address 0 means output of the
measured value as 4 … 20 mA signal.
In Multidrop mode, up to 63 sensors can be operated on one two-wire
cable. An address between 1 and 63 must be assigned to each sen-
sor.
1)
The default setting is standard with address 0.
The instrument settings are copied with this function. The following
functions are available:
•
Store data from the sensor into the indicating/adjustment module.
•
Store data from the display and adjustment module in the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
•
All data of the menu "
Setup
" and "
Display
"
•
In the menu "
Additional settings
" the items "
Distance unit, tem-
perature unit and linearization
"
•
The values of the user programmable linearization curve
Additional adjustments -
HART mode
Additional adjustments -
Copy instrument settings
1)
The 4 … 20 mA signal of the HART sensor is switched off. The sensor
consumes a constant current of 4 mA. The measuring signal is transmitted
exclusively as digital HART signal.