77
12 Supplement
VEGAFLEX 82 • 4 … 20 mA/HART - two-wire
44222-EN-170220
4
5
3
1
2
4
5
3
1
2
Fig. 44: Measuring ranges - VEGAFLEX 82
1 Reference plane
2 Probe length L
3 Measuring range
4 Upper dead band (see following diagrams - grey section)
5 Lower dead band (see following diagrams - grey section)
Typical deviation
6)
See following diagrams
L
0
-2mm
(-0.079")
2mm
(0.079")
15mm
(0.591")
-10mm
(-0.394")
0,3 m
(11.811")
0,08 m
(3.15")
0,02 m
(0.787")
1
Fig. 45: Deviation VEGAFLEX 82 in rod version
1 Dead band (no measurement possible in this area)
L Probe length
6)
Depending on the mounting conditions, deviations can occur which can be rectified by adapting the adjustment
or changing the measured value offset in the DTM service mode.