7 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART - two-wire
44222-EN-170220
Menu
Menu item
Default value
Setup
Scaling variable - Level
Volume in l
Scaling unit - Level
Litres
Scaling format - Level
Without decimal positions
Scaling level - 100 % corresponds to
100
Scaling level - 0 % corresponds to
0
Accept scaling of the level measurement
Yes
Scaling variable - Interface
Volume
Scaling unit - Interface
Litres
Scaling format - Interface
Without decimal positions
Scaling interface - 100 % corresponds to
100
Scaling interface - 0 % corresponds to
0
Setup
Current output, output variable
First HART variable (PV)
Lin. percent - Level
Current output - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output - Reaction in case of failure
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Current output 2 - Output variable
Second HART variable (SV)
Distance - Level
Current output 2 - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output 2 - Reaction in case of fault
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Third HART variable (TV)
Measurement certainty, level
Fourth HART variable (QV)
Electronics temperature
Menu - Display
Menu
Menu item
Default value
Display
Language
Order-specific
Displayed value 1
Filling height Level
Displayed value 2
Electronics temperature
Backlight
Switched on