10 Diagnostics and servicing
VEGAFLEX 82 • 4 … 20 mA/HART - two-wire
44222-EN-170220
7. Cable: Fasten the cable with three pins, torque 20 Nm
(14.75 lbf in)
Cable ø 4: 7 Nm (5.16 lbf ft)
Cable ø 6, cable ø 8: 20 Nm (14.75 lbf ft)
8. Enter new probe length and then carry out a fresh adjustment
(see "
Setup procedure, Carrying out min. adjustment - Carrying
out max. adjustment
").
3
1
2
2
A
B
45 mm (1.77")
150 mm (5.91")
70 mm (2.76")
150 mm (5.91")
Fig. 39: Shortening the cable probe
A Gravity weight - cable ø 4 mm
B Gravity weight - cable ø 6 mm
1 Threaded pins
2 Thread M12 for eye-bolt
3 Threaded pins
10.7 Software update
The following components are required to update the sensor soft-
ware:
•
Sensor
•
Voltage supply
•
Interface adapter VEGACONNECT
•
PC with PACTware
•
Current sensor software as file
You can find the actual sensor software as well as detailed infor-
mation of the procedure in the download area on our homepage:
www.vega.com.
You can find information about the installation in the download file.
Make sure that you are using the correct software with SIL qualifica-
tion.
Instruments with SIL qualification can only be updated with a respec-
tive software. An accidental update with a wrong software version is
impossible.