70
11.12.5
Quick Install - network
No.
Description
1
Country ID
2
Values of the network parameters
3
Operating mode section
4
Values for the idle power
5
Values for the power restriction
6
Back / Cancel / Finish
•
Click
Finish to complete the installation.
•
The energy store is operational when the on/off switch is lit up green.
If the display of the LED ring on the on/off switch continues to light up red or flashes red,
the following remedial measures are to be taken:
Possible fault: The current sensor check failed. Switch the energy store “OFF” and then “ON” again after a
waiting time of approximately 90 seconds.
If the LED ring continues to flash red after the restart (duration approximately 3 minutes): Check the connection
to the current sensor and the phase assignment.
Should the LED ring continue to flash red, contact VARTA.