40
The distance to adjacent installations must be approximately 5 cm to the right and approximately 10 cm to the
left. A space of approx. 120 cm in depth in front of the device is required to be able to perform installation and
maintenance work via the front door. To ensure that escape is possible, the swivel range of doors must not
extend into this space.
The screws to open the storage cabinet on the left beside the front door must be accessible. A gap of at least
30 cm in height must be provided for above the storage cabinet. The gap between the wall and the back of the
cabinet must remain clear so that the cooling air can escape unhindered from the device.
11.4.2
Environmental conditions
The setup site must correspond to a soiling grade of 2.
It must be ensured that a continuous exchange of air takes place, perhaps by means of external ventilation e.g.
windows, air-conditioning system, ventilation or similar.
•
The distance to the ventilation must be at least 100 cm.
•
The room temperature must always be b5 °C and 30 °C (opt18 °C), the relative
humidity < 80%.
Our recommendation:
A well-ventilated room without external heat sources.
11.4.3
Non-permitted locations and environmental conditions
Altitudes above 2,000 metres, garages, carports or other locations where the environmental conditions are not
complied with.
Locations:
•
Living and bedrooms,
•
with an explosive atmosphere,
•
in which flammable or oxidising substances are stored,
•
wet rooms,
•
with large changes in ambient temperature,
•
with direct solar radiation,
•
with a humidity of over 80% and condensation,
•
in which the freezing point can be exceeded,
•
into which salty moisture can penetrate,
•
with an ammoniacal environment.
Ensure sufficient protection from rodents.
Smoking is prohibited at the setup site!