43
11.7
Connection plans of the VARTA element backup
The regulations of the country-specific standards, such as DIN VDE 0100, are to be complied with.
Meter concepts are to be coordinated with the electricity grid operator.
11.7.1
VARTA element backup with replacement power box in the TT network
1
Q2 Residual current device type B I
∆
n 30 mA
2
F2 Circuit breaker 6 A type B
3
Three sockets for consumers entitled to replacement power
To prevent electrical accidents: Label the distributor for the replacement power.
4
Subdistribution
5
House connection
6
Equipotential bus bar
7
F5 Line protection/fuse house connection
8
Consumption and feed-in meter
9
Current sensor
10
F4 Circuit breaker according to converter regulation
11
Converter for photovoltaic systems
12
Q1 Residual current device type A I
∆
n 30 mA
13
F1 Circuit breaker 16 A type B 6 kA
14
Integrated network connection (black)
15
Replacement power connection (light grey)
16
VARTA element backup with integrated section switches according to AR 4105
17
X1 Feed clamp for energy store