105
16.2
Carrying out a move
Danger
Improper further use of the battery modules
Possible danger to life and material damage.
Continue to use the battery modules exclusively in the energy store from which
they were dismounted.
WARNING
Improper transport due to lack of specialist knowledge.
Possible danger to life and material damage!
The energy store and its components may be transported only by the
manufacturer and electrical specialists qualified and certified by the
manufacturer.
Operate carefully during transport.
Adhere to the transport regulations.
Read the operating manual.
i
The opening of the storage cabinet and the dismount of the components are described
in chapter 13.10, beginning on page 93.
The battery modules are to have a
charging status of
20 to 30%
of their capacity. If
necessary, charge or discharge the battery modules.
The battery modules must be recommissioned by a qualified electrical specialist
certified by VARTA within
11 weeks
after the dismount.
i
Commissioning after a move takes place as described in chapter 8.