Technical data
Radar Tank Gauge
88
Installation and Operations Manual
Auxiliary energy
Electrical connection
Housing T 12 with separate terminal compartment.
Load HART
Minimum load for HART communication: 250
Ω
Cable entry
Cable gland: M20x1.5 or Pg13.5
Cable entry: G ½ or ½ NPT
Supply voltage
See page 28
Power consumption
Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V.
Current consumption
Max. 21 mA (50 mA inrush current).
Power supply
For stand alone operation recommended via e.g. Varec RN 221N/Z.
Performance characteristics
Reference operating
conditions
According to OIML R85:
• Temperature = –25…+55 °C (-13…+131 °F)
• Atmospheric pressure
• Relative humidity (air) = 65 % ±15%
• Medium properties: e.g. medium with good reflectivity and calm
surface.
• Tank diameter: signal beam hits the tank wall only at one side.
Note!
No major interference reflections inside the signal beam.
Maximum measured
error
Absolute accuracy: 0.5 mm (2
σ
value)
Inventory Control Versios: ±3 mm
Proof of accuracy for
custody transfer ver-
sions
The accuracy of each 7500 RTG is established through a calibration
certificate that records the absolute and relative error at 10
equidistant points during the final test. For stilling well measurements
with 7532 RTG, a NMI / PTB calibrated tape with an absolute accuracy
of 0.25 mm is used.
Each 7500 RTG is delivered with the PTB and NMi type approval.
Additional initial factory verifications for custody applications are
available on demand for all 7500 RTG.
Maximum fill speed
By the first pass trough of measuring range: 100 mm/min., after it
unlimited.
Non-repeatability
0,3 mm (1/64")
Hysteresis
0.3 mm
Resolution
digital: 0.1 mm
analogue: 0.03 % of measuring range
Settling time
Typical 15 sec
Long-term drift
The long-term drift is within the specified accuracy.
Influence of ambient
temperature
Within the specified accuracy according to OIML R85.
Software reliability
The software used in the 7500 RTG fulfills the requirements of OIML
R85. This particularly includes:
• cyclical test of data consistency
• non-volatile memory
• segmented data storage
The 7500 RTG continuously monitor the compliance with accuracy
requirements for custody transfer measurements according to OIML
R85. If the accuracy cannot be maintained, a specific alarm is
generated on the local display and via the digital communication.
Summary of Contents for 7532
Page 31: ...31 7532 Operation 5 Operation 5 1 Quick operation guide...
Page 44: ...Operation Radar Tank Gauge 44 Installation and Operations Manual...
Page 46: ...Commissioning Radar Tank Gauge 46 Installation and Operations Manual 6 3 Basic Setup...
Page 72: ...Commissioning Radar Tank Gauge 72 Installation and Operations Manual...
Page 74: ...Maintenance Radar Tank Gauge 74 Installation and Operations Manual...
Page 76: ...Accessories Radar Tank Gauge 76 Installation and Operations Manual...
Page 77: ...77 7532 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting instructions...
Page 91: ...91 7532 Appendix 11 Appendix 11 1 Operating menu HART Display modul ToF Tool...
Page 105: ...7532 IOM027FVAE0804 105 Notes...