53
7532
Commissioning
Note!
If
bypass
or
stilling well
was selected in the "
tank shape
"
(002)
function, the pipe
diameter is requested in the following step.
Function "pipe diameter" (007)
This function is used to enter the pipe diameter of the stilling well or bypass pipe.
Microwaves propagate slower in pipes than in free space. This effect depends on the
inside diameter of the pipe and is automatically taken into account by the 7500 RTG. It
is only necessary to enter the pipe diameter for applications in a bypass or stilling well.
If mounting the 7532 RTG on stilling wells with a widening of the pipe, the
inner
diam-
eter of the lower part of the pipe (d2 in the Fig.) must be entered. This is the part of the
stilling well, where the measurement is actually performed.
Function "dist./ meas. value (008)"
The
distance
measured from the reference point to the product surface and the
level
calculated with the aid of the empty adjustment are displayed. Check whether the values
correspond to the actual level or the actual distance. The following cases can occur:
• Distance correct – level correct -> continue with the next function, "
check
distance
"
(051)
• Distance correct – level incorrect -> Check "
empty calibr.
"
(005)
• Distance incorrect – level incorrect -> continue with the next function, "
check
distance
"
(051)
⇒
E
+
–
L0
0-
FM
R5
32
xx
-1
4-
00-
00
-x
x-
00
1
100%
0%
ø
d2
100%
0%
ø
⇒
E
+
–
Summary of Contents for 7532
Page 31: ...31 7532 Operation 5 Operation 5 1 Quick operation guide...
Page 44: ...Operation Radar Tank Gauge 44 Installation and Operations Manual...
Page 46: ...Commissioning Radar Tank Gauge 46 Installation and Operations Manual 6 3 Basic Setup...
Page 72: ...Commissioning Radar Tank Gauge 72 Installation and Operations Manual...
Page 74: ...Maintenance Radar Tank Gauge 74 Installation and Operations Manual...
Page 76: ...Accessories Radar Tank Gauge 76 Installation and Operations Manual...
Page 77: ...77 7532 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting instructions...
Page 91: ...91 7532 Appendix 11 Appendix 11 1 Operating menu HART Display modul ToF Tool...
Page 105: ...7532 IOM027FVAE0804 105 Notes...