49
7532
Commissioning
6.4
Basic Setup with the VU 331
Function "measured value" (000)
This function displays the current measured value in the selected unit
(see "
customer unit
"
(042)
function). The number of digits after decimal point can be
selected in the "
no.of decimals
"
(095)
function. The length of the bargraph corresponds
to the percentile value of the present measured value with regard to the span.
6.4.1
Function group "basic setup" (00)
Function "tank shape" (002)
This function is used to select the tank shape.
Note!
For the application of the 7532 RTG the selection "
stilling well
" has to be chosen in the
function "
tank shape
" (002).
Selection:
• dome ceiling
• horizontal cyl
• bypass
•
stilling well
• flat ceiling (Typical ceiling of storage tanks: a slight slope of only a few degrees can
be neglected.)
• sphere
⇒
E
+
–
⇒
E
+
–
⇒
E
+
–
L00
-FMR
2xxxx-1
4-00
-00-en-0
07
Summary of Contents for 7532
Page 31: ...31 7532 Operation 5 Operation 5 1 Quick operation guide...
Page 44: ...Operation Radar Tank Gauge 44 Installation and Operations Manual...
Page 46: ...Commissioning Radar Tank Gauge 46 Installation and Operations Manual 6 3 Basic Setup...
Page 72: ...Commissioning Radar Tank Gauge 72 Installation and Operations Manual...
Page 74: ...Maintenance Radar Tank Gauge 74 Installation and Operations Manual...
Page 76: ...Accessories Radar Tank Gauge 76 Installation and Operations Manual...
Page 77: ...77 7532 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting instructions...
Page 91: ...91 7532 Appendix 11 Appendix 11 1 Operating menu HART Display modul ToF Tool...
Page 105: ...7532 IOM027FVAE0804 105 Notes...