15
© Vallox Oy - All rights reserved
• On
— When the timer is on, the Boost mode is used only for
the period specified in the timer.
• Off
— When the timer is off, the Boost mode is used until the
mode is changed, either manually or automatically by the
week clock.
2. Proceed to the next phase by selecting
Right arrow
.
3. Use the
Plus
and
Minus
buttons to set the mode timer
duration in minutes.
4. Proceed to the next phase by selecting
Right arrow
.
5. Use the
Plus
or
Minus
buttons to set the mode fan speed as
a percentage of the maximum output ratio.
6. The fan speed is now set for the mode.
7. Proceed to the next phase by selecting
Right arrow
.
8. Use the
Plus
or
Minus
buttons to set the desired supply air
temperature for the mode. You can adjust the temperature
setting in the range +5°C ... +25°C.
9. The supply air temperature of the mode is now set.
10. Proceed to the next phase by selecting
Right arrow
.
11. Use the
Arrow
buttons to turn the automatic fan speed
control based on relative humidity of air on or off.
12. The automatic fan speed control, based on the relative
humidity of air, is now set.
13. Proceed to the next phase by selecting
Right arrow
.
14. Use the
Arrow
buttons to turn the automatic fan speed
control based on carbon dioxide or VOC level on or off.
15. The automatic fan speed control, based on the carbon
dioxide or VOC level, is now set.
16. Move to the settings of the next mode by selecting
OK
.
Fireplace mode
1. Use the
Arrow
buttons to select whether the mode timer
function is used or not. The options are:
On
— When the timer is in use.
The Fireplace mode is only used for the period specified in
the timer.
Off
— When the timer is not in use.
The Fireplace mode will be used until you (or the week
clock) change the mode.
2. The mode timer function is now set.
3. Proceed to the next phase by selecting
Right arrow
.
4. Use the
Plus
and
Minus
buttons to set the Fireplace mode
timer duration in minutes.
5. The duration of the Fireplace mode is now set.
6. Proceed to the next phase by selecting
Right arrow
.
7. Use the
Plus
and
Minus
buttons to set the supply air
fan speed of the Fireplace mode as a percentage of the
maximum output ratio.
8. The supply air fan speed of the Fireplace mode is now set.
9. Proceed to the next phase by selecting
Right arrow
.
TIP
You can browse the
settings of the Boost or
the Fireplace mode by
using the
Right arrow
button.
SETUP
TIP
It is recommended that
a higher supply air fan
speed be used in the
fireplace mode to create
overpressure in the ven-
tilation zone. Reducing
the extract air fan speed
is not recommended.
The recommended du-
ration is 15-30 min.