In addition to the transmitter's messages, the connected probes have probe-specific messages that
are also shown on the transmitter display. Messages from the connected probe start with
Probe:
. For
more information on the probe-specific messages, see the probe's documentation.
Table 8 Indigo transmitter messages shown on display
Display message
Description
Recommended action
Errors
Supply voltage out of range.
The supply voltage is below the
minimum (range: 15 ... 30 V DC
or 24 V AC ±10 % 50/60 Hz).
The error clears when the
supply voltage returns to the
specified range. Check your
power supply and restart the
transmitter if needed.
Analog output out of range.
The analog output (1 ... 3)
identified in the message has
gone out of range.
The error clears when the
output returns to range. Check
the analog output
configuration.
Warnings
Outputs configured for
different probe.
An analog output configuration
for another type of probe
already exists in the
transmitter, so the settings
cannot be received
automatically from the type of
probe you are connecting.
Configure the analog output
settings for the new probe, or
clear the analog output
configuration of the transmitter
to enable automatic receiving
of the settings.
No probe connected.
The measurement probe is not
connected, or the probe is
connected poorly and cannot
be recognized by the
transmitter.
Check that you have fastened
the probe correctly with the
locking wheel.
Unable to measure all
parameters.
Some of the measurements you
have configured to be
displayed are currently not
available. This can be caused,
for example, by the probe
heating feature: parameters
that are affected by heating
cannot be shown while the
heating cycle is ongoing.
-
Analog output test active.
Test output is being sent from
the analog output (1 ... 3)
identified in the message.
-
Analog output calibration in
progress.
The analog output (1 ... 3)
identified in the message is
being calibrated.
-
Notifications
Indigo300 User Guide
M212849EN-A
60