Adapting the unit to the heating installation 8
0020224355_00 HOME Installation and maintenance instructions
21
8.1.2
Resetting the remaining burner anti-cycling
time
▶
Hold the
button down for more than 3 seconds.
◁
is shown in the display.
8.2
Setting the pump output
Conditions
: Modulating pump
The product is equipped with a speed-regulated high-effi-
ciency pump, which adjusts independently to the hydraulic
conditions of the heating installation.
If the heating installation is equipped with a low loss header,
switch off the speed control and set the pump output to a
fixed value.
▶
If required, use diagnostics code
d.14
to adjust the set-
ting for the operating-mode-dependent pump speed.
▶
Set the diagnostics code. (
→
Page 15)
Overview of diagnostics codes (
→
Page 30)
Flow rate-pressure curves for 25 kW
(pressure measured downstream of the valves)
2
1
3
4
60
70
50
30
20
40
10
0
500
1000
1500 A
B
1
Maximum speed (by-
pass closed)
2
Maximum speed (de-
fault setting for the by-
pass)
3
Minimum speed (default
setting for the bypass)
4
Flow rate at maximum
output (
Δ
T = 20K)
A
Throughput in circuit
(l/h)
B
Available pressure
(kPa)
Flow rate-pressure curves for 30 kW
(pressure measured downstream of the valves)
2
1
3
4
60
70
50
30
20
40
10
0
500
1000
1500 A
B
1
Maximum speed (by-
pass closed)
2
Maximum speed (de-
fault setting for the by-
pass)
3
Minimum speed (default
setting for the bypass)
4
Flow rate at maximum
output (
Δ
T = 20K)
A
Throughput in circuit
(l/h)
B
Available pressure
(kPa)
Flow rate-pressure curves for 35 kW
(pressure measured downstream of the valves)
2
1
3
4
60
70
50
30
20
40
10
0
500
1000
1500 A
B
1
Maximum speed (by-
pass closed)
2
Maximum speed (de-
fault setting for the by-
pass)
3
Minimum speed (default
setting for the bypass)
4
Flow rate at maximum
output (
Δ
T = 20K)
A
Throughput in circuit
(l/h)
B
Available pressure
(kPa)
8.3
Setting the bypass
Conditions
: Modulating pump
If the pump operating parameter
d.14
is set to Auto (∆p
limit), the default setting must not be changed.
Caution.
Risk of material damage caused by incor-
rect setting of the high-efficiency pump
When the pressure at the bypass valve is
increased (turning clockwise), malfunctions
may occur if the pump output is set below
100%.
▶
In this case, set the pump output to
5 = 100% using diagnostics parameter
d.14.
1
▶
Regulate the pressure using the adjusting screw
(1)
.
▶
Fit the front panel. (
→
Page 10)