Installation and maintenance instructions ecoTEC exclusive 0020193968_05
Code
Parameter
Values
Unit
Increment, select, explanation
Factory
setting
Own
setting
Min.
Max.
D.091
Status DCF77
Current value
–
0: No reception
1: Reception
2: Synchronised
3: Valid
–
Not ad-
justable
D.092
actoSTOR communication
status
Current value
–
actoSTOR module detection
0: Not connected
1: Connection fault
2: Connection active
–
Not ad-
justable
D.093
Adjust Device Specific
Number
0
999
–
VU 256/5
‑
7 (H-GB) ecoTEC
exclusive 627 = 209
VUW 356/5-7 (H-GB) ecoTEC
exclusive 835 = 211
VUW 436/5-7 (H-GB) ecoTEC
exclusive 843 = 212
–
D.094
Clear fault history
0
1
–
0: No
1: Yes
–
D.095
Software version: PeBUS
participant
Current value
–
0: BMU
1: AI
2: APC
3: SMU
0
D.096
Reset to factory settings?
0
1
–
0: No
1: Yes
–
D.118
CO sensor fault number
Current value
–
1: Heater short circuit
2: Heater open circuit
3: Heater temperature control fault
4: Heater temperature plausibility
check not OK
5: Sensor short circuit/open circuit
6: Reference resistance measure-
ment not OK
7: Sensor impedence too high
8: Standby reference resistance not
OK
9: EEPROM error
10: Sensor open circuit
11: Not used
12: Sensor plausibility test fault
13: Electrical power consumption
too low
14: Electrical power consumption
too high
15: Reference voltage too low
16: Reference voltage too high
–
Not ad-
justable
D.132
Multi-occupancy
0
1
–
0: Off
1: On
0
D.145
Flue gas monitoring
0
1
–
0: Off
1: On
1