0020193968_05 ecoTEC exclusive Installation and maintenance instructions
27
Condition
: Liquid gas set
▶
If you have selected the "liquid gas" gas type, after the
start-up process is complete, affix the enclosed "Liquid
gas" conversion sticker onto the data plate and affix the
enclosed tank sticker (propane quality) so that it is clearly
visible on the tank or the cylinder cabinet, if possible
close to the filler nozzle.
9.3.9
Contact data
▶
If required, store your telephone number in the
Appli-
ance config.
(max. 16 digits/no blank spaces). The oper-
ator can view the telephone number.
9.3.10 Ending the installation assistant
▶
Once you have run through the installation assistant suc-
cessfully, confirm by pressing
.
◁
The installation assistant will close and will not launch
again when the product is next switched on.
9.4
Restarting the installation assistants
Menu
→
Installer level
→
Start inst. assistant
You can restart the installation assistant at any time by call-
ing it up in the menu.
9.5
Test programmes
Menu
→
Installer level
→
Test programs
As well as the installation assistants, you can also call up
the following test programmes for start-up, service and
troubleshooting.
–
Check programs
–
Function menu
–
Electronics self-test
9.6
Using check programmes
Menu
→
Installer level
→
Test programs
→
Check pro-
grams
Display
Meaning
P.00
Purging check programme:
The internal pump is cyclically actuated.
The heating circuit and hot water circuit are purged
adaptively by automatically switching the circuits via
the automatic air vent (the cap for the automatic air
vent is loosened at the factory).
Hot water circuit
active
or
Heating circuit active
display.
1 x
: Start purging
1 x
(
Cancel
): End purge programme
Note
The duration of the purge programme is displayed by
a countdown timer. The programme then ends.
P.01
Maximum load check programme:
After successful ignition, the product is operated at
maximum heat input.
P.02
Minimum load check programme:
After successful ignition, the product is operated at
minimum heat input.
Display
Meaning
P.04
Reset eGas CH (Central Heating) check programme:
Calling up the programme deletes all of the CH cor-
rection values that have been saved from previous
calibration processes. The products then starts by
fully calibrating the combustion regulation (status
S.09
).
P.06
Filling mode check programme:
The diverter valve is moved to the mid-position. The
burner and pump are switched off (to fill or drain the
product).
P.14
Reset eGas DHW (Domestic Hot Water) check
programme:
Calling up the programme deletes all of the DHW
correction values that have been saved from previ-
ous calibration processes. The products then starts
by fully calibrating the combustion regulation (status
S.19
).
9.7
Checking and treating the heating
water/filling and supplementary water
Caution.
Risk of material damage due to poor-qual-
ity heating water
▶
Ensure that the heating water is of suffi-
cient quality.
▶
Before filling or topping up the installation, check the
quality of the heating water.
Checking the quality of the heating water
▶
Remove a little water from the heating circuit.
▶
Check the appearance of the heating water.
▶
If you ascertain that it contains sedimentary materials,
you must desludge the installation.
▶
Use a magnetic rod to check whether it contains mag-
netite (iron oxide).
▶
If you ascertain that it contains magnetite, clean the in-
stallation and apply suitable corrosion-inhibition meas-
ures, or fit a magnetic filter.
▶
Check the pH value of the removed water at 25 °C.
▶
If the value is below 8.2 or above 10.0, clean the installa-
tion and treat the heating water.
▶
Ensure that oxygen cannot get into the heating water.
Checking the filling and supplementary water
▶
Before filling the installation, measure the hardness of the
filling and supplementary water.
Treating the filling and supplementary water
▶
Observe all applicable national regulations and technical
rules when treating the filling and supplementary water.
Provided the national regulations and technical rules do not
stipulate more stringent requirements, the following applies:
You must treat the heating water in the following cases
–
If the entire filling and supplementary water quantity dur-
ing the operating life of the system exceeds three times
the nominal volume of the heating installation, or
–
If the guideline values listed in the following table are not
met, or
–
If the pH value of the heating water is less than 8.2 or
more than 10.0.