Description
of
Function
Codes
VDF730
User
Manual
-
148
-
Function
Code
Parameter
Name
Setting
Range
Default
PB
-
15
Time
interval
of
fault
auto
reset
0
.
1
–
60
.
0s
1
.
0s
It
is
used
to
set
the
waiting
time
from
the
alarm
of
the
AC
drive
to
fault
auto
reset
.
Function
Code
Parameter
Name
Setting
Range
Default
PB
-
16
Clear
time
of
fault
auto
reset
times
0
.
1
–
1000
.
0
h
1
.
0
h
When
the
running
time
of
the
AC
drive
reaches
the
value
of
this
parameter
,
the
existing
fault
auto
reset
times
is
cleared
to
0
.
Function
Code
Parameter
Name
Setting
Range
Default
PB
-
17
Input
phase
loss
protection
0
:
Disabled
1
:
Enabled
1
Only
the
VDF730
of
above
18
.
5
kW
provides
the
input
phase
loss
function
.
Function
Code
Parameter
Name
Setting
Range
Default
PB
-
18
Output
phase
loss
protection
0
:
Disabled
1
:
Enabled
1
It
is
used
to
determine
whether
to
perform
output
phase
loss
protection
.
Function
Code
Parameter
Name
Setting
Range
Default
PB
-
19
Heatsink
temperature
of
inverter
module
-
10
to
100
.
0
°
C
-
It
is
used
to
display
the
insulated
gate
bipolar
transistor
(
IGBT
)
temperature
of
the
inverter
module
.
Function
Code
Name
Setting
Range
PB
-
20
1st
fault
type
0
–
41
PB
-
21
2nd
fault
type
PB
-
22
3rd
(
latest
)
fault
type
These parameters are
used to record the types
of
the most
recent three
faults of the
AC
drive
.
The
value
0
indicates
no
fault
.
For
possible
causes
and
solution
of
each
fault
,
refer
to
Chapter
8
.
Function
Code
Parameter
Name
Description
PB
-
23
Frequency
upon
3rd
fault
It
displays
the
frequency
when
the
latest
fault
occurs
.
PB
-
24
Current
upon
3rd
fault
It
displays
the
current
when
the
latest
fault
occurs
.
PB
-
25
Bus
voltage
upon 3rd fault
It
displays
the
bus
voltage
when
the
latest
fault
occurs
.
Summary of Contents for VDF730 Series
Page 1: ...VDF730 Series...
Page 7: ......
Page 8: ...1 Safety Information and Precautions...
Page 15: ...Safety Information and Precautions VDF730 User Manual 14...
Page 16: ...2 Product Information...
Page 30: ...3 Mechanical and Electrical Installation...
Page 51: ...Mechanical and Electrical Installation VDF730 User Manual 50...
Page 52: ...4 Operation and Display...
Page 75: ...Operation and Display VDF730 User Manual 74...
Page 76: ...5 Function Code Table...
Page 97: ...Function Code Table VDF730 User Manual 96...
Page 98: ...6 Description of Function Codes...
Page 153: ...Description of Function Codes VDF730 User Manual 152...
Page 154: ...7 EMC...
Page 158: ...8 Troubleshooting...