NX-7002N Installation Manual
Page 34
05/06/13
NX-7002N
FOR PRIMARY OR BACKUP REPORTING
1.9 NX-7002N for primary reporting
The NX-7002N can be configured to be the primary transmitter. In this case, the NX-
7002N acts as the main alarm reporting device.
If the NX-7002N fails, for example, if there is no GSM coverage or there is jamming, if the
network of the provider is down or there are technical problems on the receiver side,
another device (the onboard dialler of the panel or an auxiliary dialler) can be configured
to act as backup. In this case, set location 2 to 255 (Other dialler) as backup for the NX-
7002N.
If another dialler is used as the backup device:
Enable the Autotest report options in that dialler.
Ensure that the reporting format used in the backup device is the same as the
reporting format used in the NX-7002N.
If the NX-7002N fails to report over the GPRS network to the IP receiver, you can use a
second report control from the NX-7002N as backup. For example, use SMS reporting as
the backup report control. In this case, set location 1 to 1 (TCP/IP1) and location 2 to 5
(SMS1).
1.10 NX-7002N for backup reporting
The NX-7002N can be configured to transmit events only when the primary dialler (control
panel, auxiliary dialler) fails to do so. In this case, the NX-7002N acts as the backup
reporting device.
The NX-7002N can be configured as the backup device of the control panel in two
ways:
1. Backup reporting using a report control (TCP/IP or SMS)
Select the desired report control in location 1 and set the corresponding report control as
a secondary (backup) report control in location 25.
2. Backup reporting using the GSM voice channel
In this case, the NX-7002N acts as a transparent backup device for the control panel. No
programming in the NX-7002N is required, except for the SIM PIN code in location 169.
All event reporting is programmed in the control panel.
The phone number must be programmed twice in the control panel:
Program phone number 1 as usual. For example, 011234567.
Enter a “10” in front of phone number 2. For example,
10
011234567. This forces the
NX-7002N to dial the phone number instead of the control panel.
The special audio cable (included) must be stuffed between the NX-7002N and the
control panel. See
NX-7002N layout and description