NX-7002N Installation Manual
Page 13
05/06/13
1.7 Testing the RSSI value
During the enrolling procedure, it is mandatory to check the RSSI value (signal strength)
of the NX-7002N GPRS module and record it in the system documentation. The RSSI
value is linked to the signal level of the GSM network and ranges from 0-31 with 99 as
unknown. The RSSI value may change due to environmental circumstances, for example,
additional furniture or metal constructions. If an RSSI reading is not satisfactory, move the
antenna to get a better reception.
VALUE
DESCRIPTION
Between 1 and 4
The module will not work properly and must be moved to
another location.
Between 5 and 9
The module will work but ideally should be moved to
another location.
Between 10 and 16
These are normal working values for the module located at
a longer distance from the receiver.
Above 17
Perfect conditions.
Enter programming mode.
Press
78#
to select the NX-7002N GPRS module.
Press
172#
to select the
Current GPRS RSSI
location.
Note the RSSI reading and quit programming.
1.8 Testing the GSM and GPRS connection
Enter programming mode.
Press
78#
to select the NX-7002N GPRS module.
Press
174#
to select the
Device status flags
location.
Check that the SIM card PIN is not blocked: option 1 and option 2 should be ON.
Check that the SIM card is logged onto the GSM network: option 3 should be ON.
Verify if the module is logged into the GPRS network: option 7 should be ON.
Quit programming mode.
See
NX-7002N layout and description
for an overview of the different Status LED’s on the
NX-7002N.