MIN. SUPPLY TEMP. (IDLE STATUS)
In this menu the minimum available supply temperature
for the zone, while meltaway status is
IDLE
, can be set.
The supply temperature is not allowed to fall below this
value.
This menu is only shown if
Zone Setup
is set to
Meltaway
for the zone.
To set the minimum available supply temperature:
1. Select
Min. supply temp
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5.0 ˚C
Setting range: 0.0 – 25.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
MAX. SUPPLY TEMP. (IDLE STATUS)
In this menu the maximum available supply temperature
for the zone, while meltaway status is
IDLE
, can be set.
The supply temperature is not allowed to rise above this
value.
This menu is only shown if
Zone Setup
is set to
Meltaway
for the zone.
To set the minimum available supply temperature:
1. Select
Max. supply temp
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 15.0 ˚C
Setting range: 0.0 – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply
temperature in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than the set limit during the time set in
Deviation alarm delay
, the alarm is triggered.
To set the deviation alarm limit:
1. Select
Deviation alarm limit
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation
alarm limit in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than
Deviation alarm limit
during the set
delay, the alarm is triggered.
To set the deviation alarm delay:
1. Select
Deviation alarm delay
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
4. Confirm the new setting by pressing the navigation
wheel again.