![Uponor Smatrix Move PRO Installation And Operation Manual Download Page 67](http://html1.mh-extra.com/html/uponor/smatrix-move-pro/smatrix-move-pro_installation-and-operation-manual_1060916067.webp)
VALVE CLOSE
In this menu a function to close the mixing valve, when
requirements are met, is enabled.
To enable the function:
1. Select
Valve Close
.
2. Press the navigation wheel to confirm selection.
3. Select
Enable
.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation
wheel again.
SHUT OFF OUTDOOR TEMP.
In this menu the function to stop the circulation pump
and/or when to close the mixing valve, at an outdoor
temperature setpoint is enabled/disabled for the zone.
This menu is only shown if
Pump Stop
and/or
Valve
Close
is enabled.
To set an shut off outdoor temperature:
1. Select
Shut Off Outdoor Temp.
.
2. Press the navigation wheel to confirm selection.
3. Select
Enable
.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation
wheel again.
T. OUTDOOR SETPOINT
In this menu the outdoor temperature setpoint for
stopping the circulation pump, and/or closing the
mixing valve, in the zone is set.
This menu is only shown if
Shut Off Outdoor Temp.
is enabled.
To set an outdoor temperature setpoint:
1. Select
T Outdoor Setpoint
.
2. Press the navigation wheel to confirm selection.
3. Select
Enable
.
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation
wheel again.
T. OUTDOOR DELAY
In this menu the time delay for how long the outdoor
temperature must be equal or higher than
T Outdoor
Setpoint
before stopping the circulation pump, and/or
closing the mixing valve, in the zone is set.
This menu is only shown if
Shut Off Outdoor Temp.
is enabled.
To set the stop time:
1. Select
T. Outdoor Delay
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation
wheel again.