Uponor Smatrix Move PRO Installation And Operation Manual Download Page 10

r

eal

 

time

 

CloCk

To facilitate accurate scheduling, the controller contains 
a real time clock. If an Uponor Smatrix Base PRO system 
is connected it will act as a time master, pushing the 
current time setting to the Move PRO controller.

C

omfort

 

and

 eCo 

modes

 (

sCHeduling

)

With the integrated timer in the controller, it is possible 
to change the temperature setpoint modes between 
two different temperatures. To utilise the Comfort and 
ECO modes in a zone, the zone must be setup as 

Stand 

Alone Control

 and using an room sensor. Available 

modes are 

Comfort

and 

ECO

 (economy). 

See example 

of Comfort and ECO mode below.

0 h 00

24 h 00

18 h 00

12 h 00

6 h 00

Comfort
ECO

Schedule 1

night

morning

afternoon

night

Other zones can, depending on system setup, 
simultaneously switch between Comfort and ECO mode 
according to their own programmed schedules.

0 h 00

24 h 00

18 h 00

12 h 00

6 h 00

Comfort

ECO

Schedule 2

night

morning

afternoon

night

Even if programmed schedules exist in the system, some 
zones may still operate without any scheduling. These 
zones will operate in constant Comfort mode and is not 
affected by the programming of other zones.

s

ystem

 

integration

 

WitH

 B

ase

 Pro 

systems

The system can be integrated with an Uponor Smatrix 
Base PRO system to enable individual room control in 
the zone.

The outdoor temperature sensor is connected to 
the Base PRO system, and an additional outdoor 
temperature sensor connected to the Move PRO 
controller is not needed. The outdoor temperature 
sensor data will also be used by the other zones.

The integration is activated when a zone is setup as 

Smatrix Base PRO

 (requires that the wiring is done 

and that 

Supply Water Controller

 is activated in the 

Integration

 menu in the Base PRO interface) in the 

startup wizard on the Move PRO controller.

See section 5.10 Connect Uponor Smatrix Base PRO 
controller for more information.

See section 5.13 Startup wizard for more information.

See Uponor Smatrix Base PRO documentation for more 
information.

EN

CZ

DE

DK

EE

ES

FI

FR

HR

HU

IT

LT

LV

NL

NO

PL

PT

RO

RU

SE

SK

1 0

U P O N O R   S M AT R I X   M O V E   P R O   ·   I N S TA L L AT I O N   A N D   O P E R AT I O N   M A N UA L

Summary of Contents for Smatrix Move PRO

Page 1: ...05 2017 Uponor Smatrix Move PRO HEATI N G APPLI CATI ON EN I N STALLATI ON AN D OPERATI ON M AN UAL ...

Page 2: ...e controller to AC power 28 5 13 Alternate power inputs 28 5 14 Startup wizard 28 5 15 Pre heating concrete slab DIN 1264 4 34 6 Finishing installation 36 7 Operate the Uponor Smatrix Move PRO controller 37 7 1 Principle of operation 37 7 2 Controller layout 37 7 3 Navigating the menu system 37 7 4 Start up 37 7 5 Information button 38 7 6 Main menu 38 7 7 System Overview 39 7 8 Information 39 7 9...

Page 3: ...or is not connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and does not show evidence of tampering mishandling insufficient maintenance improper storage neglect or accidental damage before installation and being put into operation While Uponor has made efforts to ensure that the manual is accurate Uponor does not guarantee or warran...

Page 4: ...ystem uses 50 Hz 230 V AC power In case of emergency immediately disconnect the power Technical constraints Caution To avoid interference keep installation data cables away from power cables of more than 50 V 2 2 Correct disposal of this product Waste Electrical and Electronic Equipment NOTE Applicable in the European Union and other European countries with separate collection systems This marking...

Page 5: ...eeping large areas clear of snow 3 1 System overview Uponor Smatrix Move PRO consists of a controller and a wide array of sensors Together they control the supply temperature in each zone by managing the connected valve actuators and circulation pumps The zones can be setup as follows Zone Setup alternatives 1 Stand Alone Control Smatrix Base PRO 2 Stand Alone Control Smatrix Base PRO Domestic Hot...

Page 6: ...is calculated using an outdoor sensor a ground temperature sensor and a ground moisture sensor When to start or stop snow melting status Stop Idle or Meltaway is determined by using an outdoor temperature sensor and two Uponor Smatrix Move PRO Sensor Snow S 158 sensors One of S 158 sensors is used for measuring the ground temperature and the other one is used for measuring the ground moisture leve...

Page 7: ...6 49 52 55 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 1 2 3 4 2 3 4 12VDC IN 15VDC GND GND 24VAC IN Base PRO Base PRO L N 230 V 10 50 60 Hz 2 A B 21 22 23 24 25 27 28 29 30 71 72 73 74 75 76 77 78 79 80 N L 26 microSD 4 SMATRIX BASE PRO BUS 3 3 4 L N L N L N 2 3 4 L N 1 T 125 mA 1A 1A 6A 6A Base PRO L N 230 V 10 50 60 Hz 1 2 A B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 41 42 45 48 51 54 56...

Page 8: ...s designed to be embedded into outdoor surfaces to measure the ground temperature and moisture level The sensor is only used in zones setup as Meltaway To ensure the snow melting function two Uponor Smatrix Move PRO Sensor Snow S 158 and three supply return sensors must be installed Main characteristics Detects moisture Detects temperature Horizontal installation to ensure collection of draining m...

Page 9: ...ntroller is shown in the diagram below The diagram shows the calculated supply temperature for each curve at different outdoor temperatures The controller uses the selected curve to operate the mixing valve which in turn adjusts the supply temperature to the system 80 70 60 50 40 30 20 10 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 2 4 6 8 10 12 14 16 18 20 0 0 2 0 4 0 6 0 7 0 8 1 1 2 1 5 2 ...

Page 10: ...hedules exist in the system some zones may still operate without any scheduling These zones will operate in constant Comfort mode and is not affected by the programming of other zones System integration with Base PRO systems The system can be integrated with an Uponor Smatrix Base PRO system to enable individual room control in the zone The outdoor temperature sensor is connected to the Base PRO s...

Page 11: ...lation Verify the contents of the package with the packing list See also section 3 3 Uponor Smatrix Move PRO components for identification of components Study the wiring diagram in the end of this manual or on the controller L N 230 24 0 V 50 Hz 2 21 22 23 24 25 27 28 29 30 71 72 73 74 75 76 77 78 79 80 N L 26 microSD T 125 mA To determine where to best place the Uponor Smatrix Move PRO components...

Page 12: ... manual Stand Alone Control A B If the zone 1 through 4 is setup as Stand Alone Control basic control of the system is enabled The following components are required for heating operation in the zone regulate the zone temperature using a mixing valve Supply sensor S 152 Optional Room sensor S 155 The outdoor temperature sensor is not needed if the Move PRO controller is integrated with an Uponor Sm...

Page 13: ... activated in the Integration menu in the Base PRO interface in the startup wizard on the Move PRO controller See section 5 Install Uponor Smatrix Move PRO controller for more information SYSTEM SETTINGS IN STARTUP WIZARD Enable Zone 1 2 3 or 4 Yes Zone setup Smatrix Base PRO Heating Mode Outdoor outdoor temperature sensor only Outdoor Indoor comp outdoor temperature sensor with optional room temp...

Page 14: ...taway hot water production for snow melting keeping large areas clear of snow is enabled in the zone The following components are required for snow melting hot water production in the zone regulate the supply temperature using a mixing valve Required Supply sensor S 152 Return sensor S 152 Primary return sensor S 152 not shown in illustration Snow sensor S 158 used as ground temperature sensor Sno...

Page 15: ... 73 74 75 76 77 78 79 80 N L microSD L N L N 2 3 L N 1 T 125 mA A B 21 22 23 24 25 27 28 29 30 26 SMATRIX BASE PRO BUS 3 1 2 230 V 10 50 60 Hz I IN 1A I IN 6A I IN 6A Base PRO 25 26 3 microSD 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 41 42 45 48 51 54 56 44 43 47 50 53 46 49 52 55 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 1 2 3 4 2 3 4 12VDC IN 15VDC GND GND 24VAC IN Base PRO Base PRO L ...

Page 16: ...71 72 73 74 75 76 77 78 79 80 N L 26 micro SD T 125 mA 5 7 Connect sensors to controller The following sensors can be connected to the system Uponor Smatrix Outdoor S 1XX Uponor Smatrix Move Sensor Supply Return S 152 Uponor Smatrix Move PRO Sensor Room S 155 Uponor Smatrix Move PRO Sensor Snow S 158 Warning Electrical installation and service behind secured 230 V AC covers must be carried out und...

Page 17: ...he outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight 2 Ensure that the outdoor sensor is placed away from doors windows or air outlets N S E W Connect outdoor sensor to controller The illustration below shows the outdoor sensor connected to the controller 16 X 159 S 1XX To connect an outdoor sensor to the controller 1 Ensure that the power is di...

Page 18: ...ing the wires to the connector Return sensor The return sensor only needs to be installed in zones setup as Meltaway or DHW domestic hot water Connect return sensor to controller The illustration below shows return sensors connected to the controller 4 6 11 X 159 S 152 3 2 4 To connect a return sensor to the controller 1 Study the wiring diagram to locate the connection terminal positions 2 Ensure...

Page 19: ...not be heated through the wall by sunshine 4 Ensure that the room sensor is away from any source of heat for example television set electronic equipment fireplace spotlights and so on 5 Ensure that the room sensor is away from any source of humidity and water splashes IP20 1 3 1 5 m Label room sensor Label the room sensors where suitable with the zone numbers they are to control for example 02 03 ...

Page 20: ...nnection terminal positions 2 Ensure that the power is disconnected from the controller 3 Remove the terminal cover See section 5 6 Terminal cover for more information 4 Route the wires through points A or B 5 Connect the wires from the room sensor to the controller ZONE 1 Terminals 2 and 2 ZONE 2 Terminals 4 and 4 ZONE 3 Terminals 6 and 6 ZONE 4 Terminals 11 and 11 6 Tighten the screws fixing the...

Page 21: ...o allow draining melt water to collect on the sensor surface Not too deep though The snow sensor must be installed in an open unsheltered position away from walls and exposed to the elements eg not close to walls fan outlets or other sources which can affect the sensors If the snow sensor is to be used as a ground temperature sensor it must not be installed closer than 20 cm to the heating loop If...

Page 22: ... where the sensor is to be installed Make sure it is securely embedded in relation to the expected surface load 3 Insert the supplied wood plug into the sensor tube before applying the concrete asphalt 4 Apply the concrete asphalt 5 Remove the wood plug when the concrete asphalt has cured 6 Ensure that the sunsor tube is clean 7 Insert the sensor cable and route it into the cable conduit Ensure th...

Page 23: ...sensor to the controller 1 Study the wiring diagram to locate the connection terminal positions 2 Ensure that the power is disconnected from the controller 3 Remove the terminal cover See section 5 6 Terminal cover for more information 4 Connect the wires from the snow sensor to the controller ZONE 3 Pink wire to terminal 7 Grey wire to terminal 7 ZONE 4 Pink wire to terminal 12 Grey wire to termi...

Page 24: ... may only need to be installed in zones setup as Meltaway Connect primary return sensor to controller The illustration below shows primary return sensors connected to the controller 9 14 X 159 S 152 3 4 To connect a primary return sensor to the controller 1 Study the wiring diagram to locate the connection terminal positions 2 Ensure that the power is disconnected from the controller 3 Remove the ...

Page 25: ...e controller 1 Ensure that the power is disconnected from both the controller and the actuator 2 Remove the terminal cover See section 5 6 Terminal cover for more information 3 Study the wiring diagram to locate the connection terminal positions 4 Connect the wires from the actuator to the controller ZONE 1 0 10 V wire to terminal 43 Ground wire to terminal 42 ZONE 2 0 10 V wire to terminal 46 Gro...

Page 26: ... power is disconnected from the controller 2 Remove the terminal cover See section 5 6 Terminal cover for more information 3 Study the wiring diagram to locate the connection terminal positions 4 Connect power max 230VAC to the circulation pumps external relays via connection terminals on the controller Caution The terminals are limited to 1A An external relay might be needed ZONE 1 Power L from t...

Page 27: ...ntation for more information 4 Study the wiring diagrams of both controllers to locate the connection terminal positions 5 Connect the wires from the Base PRO controller to the Move PRO controller Uponor Smatrix Base PRO Communication wire to system bus terminal A B and Uponor Smatrix Move PRO Communication wire to system bus terminal 21 22 A and 23 B 6 Tighten the screws fixing the wires to the c...

Page 28: ...cket or if required by local regulations to a junction box 5 13 Alternate power inputs The controller has connection terminals for alternate power inputs connection terminals 52 56 Caution Do not use these input terminals unless instructed to by Uponor technical support 5 14 Startup wizard The controller initiates a startup wizard the first time it is started or after a factory reset This wizard i...

Page 29: ... system Language English Deutsch Espanol Swedish 2 Set the time Set the time of the system starting with the hours Time Enter the hours hh mm 12 34 Time Enter the minutes hh mm 12 34 3 Set the date Set the date of the system starting with the day Date Enter the day Tue 01 06 2016 Date Enter the month Tue 01 06 2016 Date Enter the year Tue 01 06 2016 EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL ...

Page 30: ...O controller Stand Alone Control or to a connected Base PRO controller Smatrix Base PRO See section 5 7 Connect sensors to controller Outdoor sensor for more information Heating Mode Outdoor Outdoor Indoor comp 5 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a h...

Page 31: ...etup menu Heating Mode Outdoor Outdoor Indoor comp 6 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a heating demand with the highest setpoint value in the zone Average calculates the average from all connected room thermostats in the zone selected in the Smatrix...

Page 32: ...u Heating Mode Outdoor Outdoor Indoor comp 7 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a heating demand with the highest setpoint value in the zone Average calculates the average from all connected room thermostats in the zone selected in the Smatrix Base PR...

Page 33: ...u Heating Mode Outdoor Outdoor Indoor comp 8 4 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature Worst Case uses the room temperature from the room only rooms with a heating demand with the highest setpoint value in the zone Average calculates the average from all connected room thermostats in the zone selected in the Smatrix Base PR...

Page 34: ...e heating is run in three different phases Pase 1 The supply temperature setpoint is set to 25 C for 3 days can be set in the Settings menu Pase 2 The supply temperature setpoint is set to maximum allowed calculated setpoint for 4 days can be set in the Settings menu Pase 3 The controller enters Standby mode until the startup wizard is restarted Settings Installer Settings Restart wizard Frost pro...

Page 35: ...able to enable pre heating zone 2 in the controller Pre Heating Zone 2 Disable Enable 6 2 Set a maximum allowed calculated supply setpoint Z2 Max Calc Supply Setpoint min 5 0 max 70 0 45 0 C 7 Enable Pre Heating Zone 3 7 1 Select Enable to enable pre heating zone 3 in the controller Pre Heating Zone 3 Disable Enable 7 2 Set a maximum allowed calculated supply setpoint Z3 Max Calc Supply Setpoint m...

Page 36: ...ach the terminal covers to the controller 3 Check the mixing valves Increase the setpoints in each zone to make sure the valves are opening correctly 4 Set system parameters in the controller to the defined operating settings 5 Print and fill in the Installation report located at the end of the manual 6 Give the manual and all information about the system to the user EN CZ DE DK EE ES FI FR HR HU ...

Page 37: ...iption A Display B Navigation wheel OK button Used for navigating the menu system selecting options and confirming selections C Information button Used for showing current zone information such as supply temperature pump status etc Push the button repeatedly to switch zones D Back button 7 3 Navigating the menu system Select change Turn the control wheel to select an option or to change a paramete...

Page 38: ...us Domestic Hot Water The following information is shown if the zone is setup as Domestic Hot Water Supply Temperature current supply temperature Pump status Mixing valve status Meltaway The following information is shown if the zone is setup as Meltaway Supply Temperature current supply temperature Outdoor Temperature current outdoor temperature Status current meltaway statu Stop Idle Melting Pro...

Page 39: ...stem information menu shows the current time and date Zone 1 Information This menu shows information about zone 1 Menu tree Zone 1 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint Indoor temperature ECO Comf Status Mixing Valve Pump Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration Zone Setup ...

Page 40: ...on is only shown if Zone Setup is set to Stand Alone Control Zone 2 Information This menu shows information about zone 2 Menu tree Zone 2 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint DHW Circ Return Temp Indoor temperature ECO Comf Status Mixing Valve Pump Parts of the menu tree may only be visible in the Move PRO controller depending on its curre...

Page 41: ...g Valve The status of the mixing valve is shown 0 supply from heat source closed 100 supply from heat source fully opened Pump The status of the circulation pump is shown on off This information is only shown if Zone Setup is set to Stand Alone Control or Domestic Hot Water Zone 3 Information This menu shows information about zone 3 Menu tree Zone 3 Information Zone Setup Heating Mode Heating Curv...

Page 42: ...or the zone This information is only shown if Zone Setup is set to Meltaway Return temperature The current return temperature is shown This information is only shown if Zone Setup is set to Meltaway Ground Temperature The current temperature in the ground around the snow sensor is shown This information is only shown if Zone Setup is set to Meltaway Ground Moisture This parameter shows if there is...

Page 43: ...ntrol or Smatrix Base PRO Supply temperature The current supply temperature is shown The temperature is measured by the supply temperature sensor wired to the controller Calculated Supply Setpoint The calculated supply temperature is shown The setpoint is calculated using the sensor setup selected in Heating Mode Indoor temperature The current indoor temperature for the zone is shown If the zone i...

Page 44: ...tion Protecting the heat source from low return temperatures The status may change in case of sensor fault An alarm will also be shown in the display if that is the case This information is only shown if Zone Setup is set to Meltaway Mixing Valve The status of the mixing valve is shown 0 supply from heat source closed 100 supply from heat source fully opened Pump The status of the circulation pump...

Page 45: ...n wheel to confirm selection Alarm history This menu shows a list of the 10 latest alarms in the controller Each active alarm is presented with a short description about when it was logged and why it occured Detailed information is available via button press The detailed information shows alarm type time and date when it was logged the source of the alarm with severity PR1 to PR5 where PR5 is the ...

Page 46: ...m selection 3 Set the value Default 0 C Setting range 50 50 C 1 C increments 4 Confirm the new setting by pressing the navigation wheel again Lock code A lock code can be used to block a user from changing parameter settings The menu system is fully accessible but the lock code is required to enter and change parameter settings The default lock code is 0000 It is recommended to change this code if...

Page 47: ...Select Display contrast 4 Press the navigation wheel to confirm selection 5 Set the display contrast Setting range 50 100 1 increments 6 Press the navigation wheel to confirm selection Restore factory settings This menu enables all parameter settings in the controller to be reset to the factory default settings To restore the factory settings 1 Select Restore factory settings 2 Press the navigatio...

Page 48: ...Zone 1 Settings Supply Temp Settings Indoor Temp Settings Comf ECO Heating Curve Manual Operation Pump Mixing Valve Seasonal Shut Off Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration Supply Temp Settings This menu enables access to settings related to the supply temperature in the zone MENU TREE Supply Temp Settings Calculated Supply Setp...

Page 49: ...limit for the supply temperature in the zone is set If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay the alarm is triggered To set the deviation alarm limit 1 Select Deviation alarm limit 2 Press the navigation wheel to confirm selection 3 Set the value Default 10 0 C Setting range 0 0 50 0 C 0 ...

Page 50: ... set If the measured indoor temperature is higher than the indoor temperature setpoint the supply temperature sepoint will be lowered using this value This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint NOTE If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating To set the ...

Page 51: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Page 52: ...wheel again HEATING CURVE This menu shows the heating curve and max min supply temperature limits for the zone Manual Operation This menu enables access to manual operation mode in the zone When manual operation mode is activated access to manual control override of the circulation pump and mixing valve is enabled MENU TREE Manual Operation Manual Mode Pump Mixing valve Parts of the menu tree may ...

Page 53: ...the week for pump exercise is set This menu is only shown if Pump Exercise is set to Pump Exercise To select a day of the week for pump exercise 1 Select Exercise Day of the Week 2 Press the navigation wheel to confirm selection 3 Select a day Setting range Monday Sunday 4 Confirm the setting by pressing the navigation wheel again EXERCISE HOUR In this menu the hour of the day for pump exercise is...

Page 54: ...the I time 1 Select I time 2 Press the navigation wheel to confirm selection 3 Set the value Default 35 seconds Setting range 5 300 seconds 1 second increments 4 Confirm the setting by pressing the navigation wheel again ACTUATOR RUNNING TIME In this menu the actuator running time for the mixing valve regulation is set To set the actuator running time 1 Select Actuator running time 2 Press the nav...

Page 55: ... CLOSE In this menu a function to close the mixing valve when requirements are met is enabled To enable the function 1 Select Valve Close 2 Press the navigation wheel to confirm selection 3 Select Enable Default Disable Setting range Disable Enable 4 Confirm the setting by pressing the navigation wheel again SHUT OFF OUTDOOR TEMP In this menu the function to stop the circulation pump and or when t...

Page 56: ... OFF INDOOR TEMP In this menu the function to stop the circulation pump and or when to close the mixing valve at an indoor temperature setpoint is enabled disabled for the zone This menu is only shown if Pump Stop and or Valve Close is enabled and if Heating Mode is set to Outdoor Indoor comp for the zone To set an shut off outdoor temperature 1 Select Shut Off Outdoor Temp 2 Press the navigation ...

Page 57: ...ature is used as setpoint for the supply temperature This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone To override the calculated supply setpoint 1 Select Calculated supply setpoint 2 Press the navigation wheel to confirm selection 3 Select Manual 4 Set the override value Setting range 5 0 70 0 C 0 1 C increments 5 Confirm the new setting by press...

Page 58: ...e overheating alarm limit for domestic hot water production is set If the supply temperature is higher than the set limit during the time set in Overheating alarm delay the alarm is triggered This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone To set the overheating alarm limit 1 Select Overheating alarm limit 2 Press the navigation wheel to confirm selection 3 Set the ...

Page 59: ... Stand Alone Control Smatrix Base PRO Default 5 min Setting range 0 30 min 1 min increments Domestic Hot Water Default 60 seconds Setting range 0 600 seconds 1 second increments 4 Confirm the new setting by pressing the navigation wheel again Indoor Temp Settings This menu enables access to settings related to the room temperature sensor in the zone This menu and its submenus are only shown if Hea...

Page 60: ...r Setpoint Influence Lower 2 Press the navigation wheel to confirm selection 3 Set the value Default 4 0 C Setting range 0 0 10 0 C 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again INDOOR SETPOINT INFLUENCE UPPER In this menu the indoor setpoint influence upper is set If the measured indoor temperature is lower than the indoor temperature setpoint the supply temper...

Page 61: ...C 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again BOOSTPOWER In this menu the boost power for domestic hot water production is set The parameter is used to adjust the calculated supply temperature if the difference between the supply and return temperatures is to large This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone To set the boost...

Page 62: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Page 63: ...wheel again HEATING CURVE This menu shows the heating curve and max min supply temperature limits for the zone Manual Operation This menu enables access to manual operation mode in the zone When manual operation mode is activated access to manual control override of the circulation pump and mixing valve is enabled MENU TREE Manual Operation Manual Mode Pump Mixing valve Parts of the menu tree may ...

Page 64: ...ller depending on its current configuration PUMP EXERCISE In this menu pump exercise can be activated To activate pump exercise 1 Select Pump Exercise 2 Press the navigation wheel to confirm selection 3 Select Pump Exercise Default No Exercise Setting range No Exercise Pump Exercise 4 Confirm the new setting by pressing the navigation wheel again EXERCISE DAY OF THE WEEK In this menu the day of th...

Page 65: ...wheel to confirm selection 3 Set the value Default 0 min Setting range 0 59 min 1 min increments 4 Confirm the setting by pressing the navigation wheel again Mixing Valve This menu enables access to mixing valve settings in the zone MENU TREE Mixing Valve P area I time Actuator running time P AREA In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Pr...

Page 66: ...conds 1 second increments 4 Confirm the setting by pressing the navigation wheel again Seasonal Shut Off This menu enables access to seasonal shut off settings in the zone This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO MENU TREE Seasonal Shut Off Pump Stop Valve Close Shut Off Outdoor Temp T Outdoor Setpoint T Outdoor Delay Shut Off Indoor Temp T Indoor Del...

Page 67: ...utdoor temperature setpoint for stopping the circulation pump and or closing the mixing valve in the zone is set This menu is only shown if Shut Off Outdoor Temp is enabled To set an outdoor temperature setpoint 1 Select T Outdoor Setpoint 2 Press the navigation wheel to confirm selection 3 Select Enable Default 17 0 C Setting range 0 0 40 0 C 0 1 C increments 4 Confirm the setting by pressing the...

Page 68: ...5 h 1 h increments 4 Confirm the setting by pressing the navigation wheel again Zone 3 Settings In this menu parameter settings for zone 3 can be set or changed Menu tree Zone 3 Settings Supply Temp Settings Indoor Temp Settings Comf ECO Heating Curve Meltaway Curve IDLE Status Return Temperature Enter Stop State Conditions Enter Idle State Conditions Enter Melting State Conditions Manual Operatio...

Page 69: ... 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again MAX SUPPLY TEMP In this menu the maximum allowed supply temperature for the zone can be set The supply temperature is not allowed to rise above this value This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO To set the maximum allowed supply temperature 1 Select Max supply temp 2 P...

Page 70: ...ng by pressing the navigation wheel again DEVIATION ALARM LIMIT In this menu the deviation alarm limit for the supply temperature in the zone is set If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay the alarm is triggered To set the deviation alarm limit 1 Select Deviation alarm limit 2 Press the...

Page 71: ... the measured indoor temperature is higher than the indoor temperature setpoint the supply temperature sepoint will be lowered using this value This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint NOTE If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating To set the indoor ...

Page 72: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Page 73: ... menu enables access to meltaway heating curve settings for the zone while in IDLE status Settings such as the slope Setting and offset of the meltaway heating curve This menu is only shown if Zone Setup is set to Meltaway and if Heating Curve Meltaway is enabled for the zone MENU TREE Meltaway Curve IDLE Status Setting Offset Heating Curve SETTING In this menu the slope of the meltaway heating cu...

Page 74: ...he value set in Outdoor Temperature for the number of days set in Delay days This menu is only shown if Zone Setup is set to Meltaway for the zone MENU TREE Enter Stop State Conditions Outdoor Temperature Delay days OUTDOOR TEMPERATURE In this menu the outdoor temperature used to switch meltaway state between IDLE and STOP is set To set the outdoor temperature 1 Select Outdoor Temperature 2 Press ...

Page 75: ...ELTING to IDLE is set To set the outdoor temperature 1 Select Outdoor Temperature 2 Press the navigation wheel to confirm selection 3 Set the value Default 5 0 C Setting range 0 0 15 0 C 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again DELAY HOURS In this menu the number of delay hours used to switch meltaway state from STOP to IDLE is set To set the delay 1 Select...

Page 76: ...lection 3 Select Low Limit 4 Press the navigation wheel to confirm selection 5 Set the value Default 2 C Setting range 0 10 C 1 C increments 6 Confirm the new setting by pressing the navigation wheel again OUTDOOR TEMP OFFSET In this menu the outdoor temperature offset used to switch meltaway state from IDLE to MELTING is set To set the outdoor temperature offset 1 Select Outdoor Temp Offset 2 Pre...

Page 77: ...is menu the pump can be overidden and turned on or off manually To override the circulation pump operation 1 Select Pump 2 Press the navigation wheel to confirm selection 3 Select Manual 4 Select On Default Off Setting range Off On 5 Confirm the new setting by pressing the navigation wheel again MIXING VALVE In this menu the mixing valve can be overriden opened or closed manually To override the m...

Page 78: ... of the Week 2 Press the navigation wheel to confirm selection 3 Select a day Setting range Monday Sunday 4 Confirm the setting by pressing the navigation wheel again EXERCISE HOUR In this menu the hour of the day for pump exercise is set This menu is only shown if Pump Exercise is set to Pump Exercise To select an hour of the day for pump exercise 1 Select Exercise Hour 2 Press the navigation whe...

Page 79: ...the I time 1 Select I time 2 Press the navigation wheel to confirm selection 3 Set the value Default 50 seconds Setting range 5 300 seconds 1 second increments 4 Confirm the setting by pressing the navigation wheel again ACTUATOR RUNNING TIME In this menu the actuator running time for the mixing valve regulation is set To set the actuator running time 1 Select Actuator running time 2 Press the nav...

Page 80: ...by pressing the navigation wheel again VALVE CLOSE In this menu a function to close the mixing valve when requirements are met is enabled To enable the function 1 Select Valve Close 2 Press the navigation wheel to confirm selection 3 Select Enable Default Disable Setting range Disable Enable 4 Confirm the setting by pressing the navigation wheel again SHUT OFF OUTDOOR TEMP In this menu the functio...

Page 81: ... OFF INDOOR TEMP In this menu the function to stop the circulation pump and or when to close the mixing valve at an indoor temperature setpoint is enabled disabled for the zone This menu is only shown if Pump Stop and or Valve Close is enabled and if Heating Mode is set to Outdoor Indoor comp for the zone To set an shut off outdoor temperature 1 Select Shut Off Outdoor Temp 2 Press the navigation ...

Page 82: ...ng by pressing the navigation wheel again Zone 4 Settings In this menu parameter settings for zone 3 can be set or changed Menu tree Zone 4 Settings Supply Temp Settings Indoor Temp Settings Comf ECO Heating Curve Meltaway Curve IDLE Status Return Temperature Enter Stop State Conditions Enter Idle State Conditions Enter Melting State Conditions Manual Operation Pump Mixing Valve Seasonal Shut Off ...

Page 83: ... 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again MAX SUPPLY TEMP In this menu the maximum allowed supply temperature for the zone can be set The supply temperature is not allowed to rise above this value This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO To set the maximum allowed supply temperature 1 Select Max supply temp 2 P...

Page 84: ...ng by pressing the navigation wheel again DEVIATION ALARM LIMIT In this menu the deviation alarm limit for the supply temperature in the zone is set If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay the alarm is triggered To set the deviation alarm limit 1 Select Deviation alarm limit 2 Press the...

Page 85: ... the measured indoor temperature is higher than the indoor temperature setpoint the supply temperature sepoint will be lowered using this value This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint NOTE If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating To set the indoor ...

Page 86: ...dule 2 Press the navigation wheel to confirm selection The current schedule is showing 3 Select a day 4 Press the navigation wheel to confirm selection All current schedule settings are shown each line representing a switch between Comfort and ECO mode If entering the menu for the first time only one line is present showing Comf starting at 00 00 every day of the week 5 Select an existing line to ...

Page 87: ... menu enables access to meltaway heating curve settings for the zone while in IDLE status Settings such as the slope Setting and offset of the meltaway heating curve This menu is only shown if Zone Setup is set to Meltaway and if Heating Curve Meltaway is enabled for the zone MENU TREE Meltaway Curve IDLE Status Setting Offset Heating Curve SETTING In this menu the slope of the meltaway heating cu...

Page 88: ...utdoor temperature is higher than the value set in Outdoor Temperature for the number of days set in Delay days MENU TREE Enter Stop State Conditions Outdoor Temperature Delay days OUTDOOR TEMPERATURE In this menu the outdoor temperature used to switch meltaway state between IDLE and STOP is set To set the outdoor temperature 1 Select Outdoor Temperature 2 Press the navigation wheel to confirm sel...

Page 89: ...m STOP to IDLE state when the measured outdoor temperature is lower than the value set in Outdoor Temperature for the number of hours set in Delay hours The zone switches from MELTING to IDLE state when no moisture has been detected for the number of days set in Delay Surface Dry when the outdoor temperature is higher than the value set in Outdoor Temperature and when the ground temperature is hig...

Page 90: ...ons Ground Temperature Limit Outdoor Temp Offset Outdoor Temperature Low Limit Min Time in Melting GROUND TEMPERATURE LIMIT In this menu the ground temperature limit used to switch meltaway state between IDLE to MELTING is set To set the ground temperature limit 1 Select Ground Temperature Limit 2 Press the navigation wheel to confirm selection 3 Select Low Limit 4 Press the navigation wheel to co...

Page 91: ... This menu enables access to manual operation mode in the zone When manual operation mode is activated access to manual control override of the circulation pump and mixing valve is enabled MENU TREE Manual Operation Manual Mode Pump Mixing valve Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration To activate manual operation mode 1 Select Ma...

Page 92: ...depending on its current configuration PUMP EXERCISE In this menu pump exercise can be activated To activate pump exercise 1 Select Pump Exercise 2 Press the navigation wheel to confirm selection 3 Select Pump Exercise Default No Exercise Setting range No Exercise Pump Exercise 4 Confirm the new setting by pressing the navigation wheel again EXERCISE DAY OF THE WEEK In this menu the day of the wee...

Page 93: ...p exercise 1 Select Exercise Min 2 Press the navigation wheel to confirm selection 3 Set the value Default 0 min Setting range 0 59 min 1 min increments 4 Confirm the setting by pressing the navigation wheel again Mixing Valve This menu enables access to mixing valve settings in the zone MENU TREE Mixing Valve P area I time Actuator running time P AREA In this menu the P area for the mixing valve ...

Page 94: ...access to seasonal shut off settings in the zone This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO MENU TREE Seasonal Shut Off Pump Stop Valve Close Shut Off Outdoor Temp T Outdoor Setpoint T Outdoor Delay Shut Off Indoor Temp T Indoor Delay Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration PUMP STOP I...

Page 95: ...value Default 24 h Setting range 0 24 h 1 h increments 4 Confirm the setting by pressing the navigation wheel again VALVE CLOSE In this menu a function to close the mixing valve when requirements are met is enabled To enable the function 1 Select Valve Close 2 Press the navigation wheel to confirm selection 3 Select Enable Default Disable Setting range Disable Enable 4 Confirm the setting by press...

Page 96: ... 1 h increments 4 Confirm the setting by pressing the navigation wheel again Automatic Freeze Protection This menu decides when to activate automatic freeze protection during meltaway in the zone The controller will kepp the return temperature between the low and high thersholds This menu is only shown if Zone Setup is set to Meltaway for the zone MENU TREE Automatic Freeze Protection Primary retu...

Page 97: ... system is set To set the date 1 Select Date 2 Press the navigation wheel to confirm selection 3 Set the day 4 Press the navigation wheel to confirm selection 5 Set the month 6 Press the navigation wheel to confirm selection 7 Set the year 8 Confirm the setting by pressing the navigation wheel again Language In this menu the language of the system is set To set the language 1 Select Language 2 Pre...

Page 98: ...ature The current supply temperature is shown The temperature is measured by the supply temperature sensor wired to the controller State The current pre heating state phase in the zone is shown Pre heating is run in three different phases Pase 1 The supply temperature setpoint is set to 25 C for 3 days can be set in the Settings menu Pase 2 The supply temperature setpoint is set to maximum allowed...

Page 99: ...pre heating phase in the zone is shown Zone 3 Information This menu shows information about zone 3 Menu tree Zone 3 Information Supply temperature State Time Left Supply temperature The current supply temperature is shown The temperature is measured by the supply temperature sensor wired to the controller State The current pre heating state phase in the zone is shown Pre heating is run in three di...

Page 100: ...t The time left of the current pre heating phase in the zone is shown Controller Information This menu shows information about the controller Menu tree Controller Information Language About Language This menu show the set display language for the controller About This menu shows the serial number software versions and hardware versions of the controller 7 12 Pre Heating Settings In this menu insta...

Page 101: ...m selection 3 Enter the lock code in the boxes using the navigation wheel Turn the navigation wheel to either select a box or to increase decrease a value in edit mode Press the navigation wheel to enter edit mode or to confirm the new setting Default 0000 4 Confirm the lock code by pressing and holding the navigation wheel for a number of seconds 5 Change the parameter setting and exit Change loc...

Page 102: ...backup 1 Make sure the microSD card with the backup is inserted into the controller 2 Select Restore backup 3 Press the navigation wheel to confirm selection 4 Select Yes Setting range No default Yes 5 Press the navigation wheel to confirm selection 6 All parameters in the controller are being restored from backup New backup This menu enables the controller to save a backup of all parameter settin...

Page 103: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 140 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Page 104: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 200 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Page 105: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 200 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Page 106: ... supply temp 0 1 C increments 4 Confirm the new setting by pressing the navigation wheel again P area In this menu the P area for the mixing valve regulation is set To set the P area 1 Select P area 2 Press the navigation wheel to confirm selection 3 Set the value Default 200 0 C Setting range 2 0 500 0 C 0 1 C increments 4 Confirm the setting by pressing the navigation wheel again I time In this ...

Page 107: ...the setting by pressing the navigation wheel again Language In this menu the language of the system is set To set the language 1 Select Language 2 Press the navigation wheel to confirm selection 3 Select a language 4 Confirm the setting by pressing the navigation wheel again Operation mode In this menu the operation mode of the system is set This setting is used to change from pre heating to stand...

Page 108: ...ing Valve Pump Zone 2 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint DHW Circ Return Temp Indoor temperature ECO Comf Status Mixing Valve Pump Zone 3 Information Zone Setup Heating Mode Heating Curve Supply temperature Calculated Supply Setpoint Indoor temperature ECO Comf Status Meltaway Curve Return temperature Ground Temperature Ground Moisture P...

Page 109: ...tings T Outdoor Fallback Lock code Change lock code Display settings Restore factory settings Restore backup New backup Restart wizard Zone 1 Settings Supply Temp Settings Calculated Supply Setpoint Min Supply Temp Max Supply Temp Deviation alarm limit Deviation alarm delay Indoor Temp Settings Indoor Setpoint Calculated Indoor Setpoint ECO Comf Status Indoor Setpoint Influence Lower Indoor Setpoi...

Page 110: ...ed Supply Setpoint Min Supply Temp Max Supply Temp DHW Supply Setpoint Overheating alarm limit Overheating alarm delay Deviation alarm limit Deviation alarm delay Indoor Temp Settings Indoor Setpoint Calculated Indoor Setpoint ECO Comf Status Indoor Setpoint Influence Lower Indoor Setpoint Influence UPPER DHW Circ Return Settings DHW Circ Return Setpoint BoostPower Comf ECO ECO Setback ECO Comf St...

Page 111: ...Melting Supply Setpoint Min Supply Temp Max Supply Temp Heating Curve Meltaway IDLE Supply Setpoint Min Supply Temp IDLE Status Max Supply Temp IDLE Status Deviation alarm limit Deviation alarm delay Indoor Temp Settings Indoor Setpoint Calculated Indoor Setpoint ECO Comf Status Indoor Setpoint Influence Lower Indoor Setpoint Influence UPPER Comf ECO ECO Setback ECO Comf Status ECO Comf Schedule H...

Page 112: ... Low Limit Min Time in Melting Manual Operation Manual Mode Pump Mixing valve Pump Pump Exercise Exercise Day of the Week Exercise Hour Exercise Min Mixing Valve P area I time Actuator running time Seasonal Shut Off Pump Stop Valve Close Shut Off Outdoor Temp T Outdoor Setpoint T Outdoor Delay Shut Off Indoor Temp T Indoor Delay Automatic Freeze Protection Primary return Temp Low Primary return Te...

Page 113: ...Schedule Heating Curve Setting Offset Heating Curve Meltaway Curve IDLE Status Setting Offset Heating Curve Return Temperature Max Supply Return Diff Enter Stop State Conditions Outdoor Temperature Delay days Enter Idle State Conditions Outdoor Temperature Delay hours Delay Surface Dry Enter Melting State Conditions Ground Temperature Limit Outdoor Temp Offset Outdoor Temperature Low Limit Min Tim...

Page 114: ...Pre Heating Operating Mode System Overview Pre Heating Info System information Time Date Zone 1 Information Z1 Supply Temperature State Time Left Zone 2 Information Z2 Supply Temperature State Time Left Zone 3 Information Z3 Supply Temperature State Time Left Controller Information Language About Alarms Active alarms Alarm history Acknowledge all alarms Reset alarm history EN CZ DE DK EE ES FI FR ...

Page 115: ...area I time Actuator running time Zone 2 Settings Z2 Max Calc Supply Setpoint Frost Protection Setpoint P area I time Actuator running time Zone 3 Settings Z3 Max Calc Supply Setpoint Frost Protection Setpoint P area I time Actuator running time Controller Settings Time Date Language Operation mode EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 115 UPONOR SMATRIX MOVE PRO INSTALLAT...

Page 116: ...if enabled in the Move PRO controller display The pump is activated for 1 minutes during the exercise 8 3 Corrective maintenance Fallback mode If a sensor is malfunctioning or not detected the controller triggers an alarm and executes the fallback mode to maintain the temperature in the zone until the problem is resolved Resetting the controller If the controller does not work as expected for exam...

Page 117: ...u system changes after the room sensor is moved The room sensor may be influenced by an external heat source Change location of the room sensor The indicator on the mixing valve actuator does not change move The mixing valve does not open 1 Check that the mixing valve is correctly installed 2 Contact the installer 3 Replace the mixing valve The room is too warm Corresponding loop is warm even afte...

Page 118: ... installation report in the end of this document Prepare the following information before contacting an installer Installation report Drawings of the underfloor heating system if available List of all alarms including time and date 9 3 Installer instructions To determine if a problem is caused by the supply system or the control system loosen the actuators from the manifold for the room concerned ...

Page 119: ... input 24 V AC 0 7A maximum 6 A Internal fuse 125 mA Sensor inputs Supply temperature sensor NTC 10 50 C 100 C 0 1 C Return temperature sensor Room temperature sensor Outdoor temperature sensor Ground temperature sensor Snow and ice sensor Moisture sensor Snow and ice sensor ROFF Ω RON 2MΩ Outputs Mixing valves UO 0 10V IO 10 mA Snow sensor UO 24 V AC PO 10 VA Circulation pumps UIN 230 V AC IIN 1 ...

Page 120: ...5 mm flexible with ferrules 10 3 Controller layout F E J K I H G C D B L M N A Item Description A Display B Sensor input connection terminals C Mixing valve output connection terminals D Battery and transformer input connection terminals E microSD F BMS MODBUS RTU RS 232 connection G Uponor Smatrix Base PRO bus connection terminals H Snow and ice sensor output connection terminals I Circulation pu...

Page 121: ... 3 4 5 6 7 8 9 10 11 12 13 14 16 52 53 54 55 56 51 50 49 48 46 45 43 42 72 26 25 24 23 22 21 B A 73 75 76 77 78 79 80 GND 15VDC 12VDC IN GND 24VAC IN PRO PRO PRO PRO PRO PRO PRO PRO N L L N 1A 1A 1A 1A I 1A EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 121 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Page 122: ... mm 90 mm 45 mm X 159 Room temperature sensor S 155 85 mm 60 mm 80 mm 30 mm Snow sensor S 158 78 mm 63 5 mm 32 mm 60 mm EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 122 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Page 123: ...g Valve Yes Yes Yes Yes No No No No Circulation pump Yes Yes Yes Yes No No No No Smartix Base PRO Supply temperature sensor Mixing valve Yes Yes Yes Yes No No No No Circulation pump Yes Yes Yes Yes No No No No PRO PRO Smatrix Base PRO controller EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 123 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Page 124: ...Moisture sensor 1 Primary return sensor Mixing valve Yes Yes No No Circulation pump Yes Yes No No Snow and ice sensor Domestic Hot Water Supply temperature sensor Return temperature sensor Mixing valve Yes No Circulation pump Yes No EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 124 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Page 125: ...EN CZ DE DK EE ES FI FR HR HU IT LT LV NL NO PL PT RO RU SE SK 125 UPONOR SMATRIX MOVE PRO INSTALLATION AND OPERATION MANUAL ...

Page 126: ... AB MRY Virsbo Sweden Uponor Corporation www uponor com Uponor reserves the right to make changes without prior notification to the specification of incorporated components in line with its policy of continuous improvement and development ...