10.2 Technical specifications
Cables
Standard cable length
Maximum cable length
Wire gauge
Cable from controller to valve actuator
(shielded connected to ground)
0.75 m
20 m
0.2 mm² to 1.5 mm²
Cable to sensor input on controller
(shielded connected to ground)
5 m
100 m
0.6 mm²
Cable from output on controller to
external devices
5 m
20 m
Up to 4.0 mm² solid, or 2.5 mm² flexible with
ferrules
Communication cable
-
5 m
0.5 mm² to 2.5 mm²
Power cable
2 m
20 m
Up to 4.0 mm² solid, or 2.5 mm² flexible with
ferrules
10.3 Controller layout
F
E
J K
I
H
G
C
D
B
L
M
N
A
Item
Description
A
Display
B
Sensor input connection terminals
C
Mixing valve output connection terminals
D
Battery and transformer input connection terminals
E
microSD
F
BMS, MODBUS-RTU (RS-232), connection
G
Uponor Smatrix Base PRO bus connection terminals
H
Snow and ice sensor output connection terminals
I
Circulation pump output connection terminals
J
Power connection connection terminal
K
Fuse (125 mA)
L
Information button
M
Navigation wheel/ OK button
N
Back button
EN
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
1 2 0