In this menu parameter settings for zone 3 can be set or
changed.
Menu tree
Zone 3 Settings
Z3 Max. Calc. Supply
Setpoint
Frost Protection Setpoint
P-area
I-time
Actuator running time
Z3 Max. Calc. Supply Setpoint
In this menu the maximum allowed calculated supply
setpoint for the zone can be set.
To set the maximum allowed calculated supply setpoint:
1. Select
Z1 Max. Calc. Supply Setpoint
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 45.0 ˚C
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
Frost Protection Setpoint
In this menu the frost protection setpoint (minimum
available supply temperature) for the zone can be set.
The supply temperature is not allowed to fall below this
value.
To set the frost protection setpoint:
1. Select
Frost Protection Setpoint
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5.0 ˚C
Setting range: 5.0 – 20.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation
wheel again.
P-area
In this menu the P-area for the mixing valve regulation
is set.
To set the P-area:
1. Select
P-area
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation
wheel again.
I-time
In this menu the I-time for the mixing valve regulation
is set.
To set the I-time:
1. Select
I-time
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation
wheel again.
Actuator running time
In this menu the actuator running time for the mixing
valve regulation is set.
To set the actuator running time:
1. Select
Actuator running time
.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation
wheel again.