Heating Curve
This menu shows the heating curve, and max/min
supply temperature limits, for the zone.
This information is only shown if
Zone Setup
is set to
Stand Alone Control
or
Smatrix Base PRO
.
Supply temperature
The current supply temperature is shown. The
temperature is measured by the supply temperature
sensor wired to the controller.
Calculated Supply Setpoint
The calculated supply temperature is shown. The
setpoint is calculated using the sensor setup selected in
Heating Mode
.
Indoor temperature
The current indoor temperature for the zone is shown.
If the zone is setup as
Stand Alone Control
the
temperature is measured by a room temperature sensor
wired to the Move PRO controller.
If the zone is setup as
Smatrix Base PRO
the Base
PRO controller sends either
Average
or
Worst Case
(setup in the startup wizard) temperatures from the
Base PRO system.
This information is only shown if
Heating Mode
is set
to
O Indoor comp.
.
ECO-Comf Status
The current ECO/Comfort for the zone status is shown.
This information is only shown if
Zone Setup
is set to
Stand Alone Control
and
Heating Mode
is set to
O Indoor comp.
.
Meltaway Curve
This menu shows the meltaway curve, and max/min
supply temperature limits, for the zone.
This information is only shown if
Zone Setup
is set to
Meltaway
.
Return temperature
The current return temperature is shown.
This information is only shown if
Zone Setup
is set to
Meltaway
.
Ground Temperature
The current temperature in the ground around the snow
sensor is shown.
This information is only shown if
Zone Setup
is set to
Meltaway
.
Ground Moisture
This parameter shows if there is moisture around the
snow sensor.
Primary Return temperature
The current primary return temperature is shown.
This information is only shown if
Zone Setup
is set to
Meltaway
.
Status
This parameter shows the current meltaway status.
Stop: Meltaway is inactive.
Idle: Meltaway is idle and the supply temperature is
kept low to keep the zone from getting too cold.
Melting: Meltaway is active.
Protection: Protecting the heat source from low return
temperatures.
The status may change, in case of sensor fault. An alarm
will also be shown in the display if that is the case.
This information is only shown if
Zone Setup
is set to
Meltaway
.
Mixing Valve
The status of the mixing valve is shown. 0 % (supply
from heat source closed) – 100 % (supply from heat
source fully opened).
Pump
The status of the circulation pump is shown (on/off).
This information is only shown if
Zone Setup
is set to
Stand Alone Control
or
Meltaway
.