Parameters table
Diag: 24V Main Power Loss
Enables or disables the generation of the diagnostics in case of a power
failure for the outputs (VA24).
Diag: Module fail
Enables or disables the generation of the diagnostics in case of module
failure.
Diag: Output fail
Enables or disables the generation of the diagnostics in case of
overload or short circuit of the outputs.
Diag: High Noise level
Enables or disables the generation of the diagnostics in case of
detection of a high level of noise.
Diag: 24V Input power loss
Enables or disables the generation of the diagnostics in case of a power
failure on the input modules.
Fast Input response time
Slow: input filter for very noisy environment (> 50mS).
Fast: Maximum sampling frequency of the inputs (< 50mS).
The time depends on the number of inputs and outputs of the system.
Default Slow.
Mode Manifold First
If True, the integrated manifold will use the first 3 bytes of the
assigned address.
If False, the integrated manifold will use the last 3 bytes of the
assigned address.
Turn off output on Fail
Select the desired behaviour in case of master CPU ALT or loss of
communication.
Able if you want to turn off all outputs automatically.
Disable if you want to leave all the outputs in the last state. (in this
case pay attention to the dangerous conditions that may be generated
in the system).
Default “Able”
Diag: Other Module info
If Able a diagnostics will be generated for each sub module.
Diag: Electric Clamp Fail
Enables or disables the generation of diagnostics in case of an error
signal from the electric clamp (FAIL output of the electric clamp).
Diag: Clamp Command Fail
Enables or disables the generation of diagnostics in case of overload or
short circuit of one or more control outputs of the electric clamp.
Clamp Lag time
Indicate the lag time between the command of an electric clamp and
the next one (multiplicative coefficient of 5ms).
Default 30 = 150mS.
Clamp Actived at the same
Time
Indicates the number of clamps that can be activated at the same time
(1…8).
Default 8.
Keep output on Safe OP
Select the desired behaviour in case of module SAFE OP status.
DisAble if you want to automatically turn off all the outputs.
Able if you want to leave all the outputs in the latest status.
(in this case pay attention to the dangerous conditions that may be
generated in the system).
Default “DisAble”.
Note: if not configured, all the diagnostics functions are enabled (once written they keep the latest configured value).
The procedure for modifying the configuration parameters depends on the master software used.
On the next page you can see an example of the menu that appears in the “TwinCAT” software by Beckhoff.