Make sure that all connectors are perfectly screwed, and those not used are blocked
with appropriate plugs (ZJM12-, ZJM08- TSCFN24SCAT), in order to guarantee the IP65
requirements.
The maximum length of the input and / or output cables allowed is 10 meters and cables
must be shielded.
(1)
The maximal power for all clamping device modules is 32A.
(2)
The maximal power for all clamping device modules and inputs is 1,5A.
(3)
The maximal number of manageable modules is 4 (2 in case of 4 size 80 power clamps).
(4)
The voltage cannot 10% and can affect the cycle time of the connected device.
Make sure that the cable section is proper to the connected device consumption.
A voltage drop on the cables causes a slowdown in the operating cycle.
(5)
The optimized power management can be obtained by setting in the device configuration the two proper commands for
clamping devices.
By setting the number of clamping devices that need to be controlled simultaneously (1-8) and the delayed time
(25...400mS), it is possible to optimize the instantaneous power, so to choose a smaller power supply.
Therefore the master activates simultaneously more clamping devices, whose functioning will be automatically delayed
in accordance to the configurated parameters.
8 Power camps – size 50
Standard “Automatic Delayed Command”
2 simultaneous clamps 125mS delay
“Automatic Delayed Command”
2 simultaneous clamps 130mS delay