![UniVer TC Manual Download Page 42](http://html1.mh-extra.com/html/univer/tc/tc_manual_845762042.webp)
Rev.B15
Pg. 42 di 80
Status and Diagnostics - EtherNet/IP LED
LED
Color
Status
Meaning
ON/Diag
On
No error.
Flashing
Error, see error codes table for further details.
Flashing
Fatal error, see error codes table for further details..
Run/Rdy
On
Operative system completely loaded and ready.
On
Error during loading of operative system or configuration
Flashing
Boot loader mode active (6 Blink No 2
nd
Stage Loader Loaded).
Flashing
Operating system missing (2
nd
Stage Loader Loaded).
MS
On
Working (the device is correctly working)
Flashing
Standby (the device is not configurated)
On
Serious failure (the device has identified a non-recoverable error).
Flashing
Minor failure (the device has identified a recoverable error).
Off
Missing power supply (VLS24).
NS
On
Device connected.
Flashing
No connection.
(One IP address is configurated, but there is no CIP connection).
On
Double IP address.
Flashing
Connection Timeout.
Off
No configurated IP address.
OUT
SUPPLY
On
Power supply on (24VA).
(Manifold and output power supply).
Off
No power supply (24VA).
(Manifold and output power supply).
LINK 1
On
Ethernet connection on channel 1.
Off
No Ethernet connection on channel 1.
LINK 2
On
Ethernet connection on channel 2.
Off
No Ethernet connection on channel 2.
ACT 1
Flashing
Message Transmission/Receipt on channel 1..
Off
No Message Transmission/Receipt on channel 1.
ACT 2
Flashing
Message Transmission/Receipt on channel 2.
Off
No Message Transmission/Receipt on channel 2.