FIRST TIME CONTROL SETUP
SECTION B, PAGE 14
Read the line voltage with a voltmeter inside the welding control and
enter
the
value on this line.
Then press . The display will show:
where ### is the value you just entered.
After a few seconds, the display will now show:
This confirms that the baseline for the Automatic Voltage Compensation
system has been set.
B10.1 TURNING OFF AVC:
If the control is not holding steady welding
current, the
AVC
function can be turned
OFF
to see if this system is causing the
problem. To do this, press:
The display will show:
Press and the
AVC
function will be turned
OFF.
YES
LINE VOLTAGE CALIB.
LINE VOLTAGE is ###
READING LINE VOLTAGE
PLEASE WAIT
REFERENCE VOLT. =###
PROGRAM
8
9
9
AVC FUNCTION IS ON
Want to change? PUSH
the YES or NO button
YES
STEP
ENTER