The water cooled coaxial condensers in these units have copper tubing and are NOT suitable for salt or brackish water.
Do not install these units outdoors, or in any area where the surrounding temperature may drop below 32ºF.
GENERAL DATA
Model
060A
096A
120A
Nominal Cooling(Ton)
5
8
10
Cooling Performance
Gross Cooling Capacity(Btuh)
64100
101800
126000
Design CFM
2000
3200
4000
Compressor-Type
Scroll
Number Used
1
2
2
Evaporator Coil-Type
Copper Tubes, Aluminum Fins
Face Area(sq ft)
5.28
9.17
9.17
Rows/FPI
3/13
3/13
3/13
Condenser-Type
Coaxial
Number Used/Tons Capacity
1/5
2/4
2/5
Nominal Water flow rate (gpm)
15
24
30
Condenser Water Connections
1" FPT
1-1/4" FPT
1-1/4" FPT
Evaporator Fan-Type
Centrifugal, Forward Curved
Number Used
1
2
2
Diameter x Width (in)
10x10
10x8
10x8
Drive
Adjustable Belt
Motor HP (Standard/Oversize)
1/NA
1.5/2
2/3
Filters
Number Used-Size(in)
2-20x20x2
2-20x25x2
1-20x20x2
2-20x25x2
1-20x20x2
Condensate Drain Connection
3/4FPT
Weight
460
710
760
NOTE:
Cooling performance is rated at 80°F dry bulb 67°F wet bulb entering air temperature,
CFM listed, 85°F entering 95°F leaving water temperature, and water flow rate listed.
Gross capacity does not include the effect of evaporator fan motor heat.
Summary of Contents for CPH 060
Page 7: ...FORM 145 14 IOM1 908 7 Johnson Controls TYPICAL INSTALLATION LAYOUT CPH060 SHOWN LD13464...
Page 10: ...JOHNSON CONTROLS 10 FORM 145 14 IOM1 908 060 LD13465...
Page 11: ...FORM 145 14 IOM1 908 11 Johnson Controls 096 120 LD13466...
Page 18: ...JOHNSON CONTROLS 18 FORM 145 14 IOM1 908 TYPICAL SCHEMATIC...
Page 20: ...JOHNSON CONTROLS 20 FORM 145 14 IOM1 908 NOTES...
Page 21: ...FORM 145 14 IOM1 908 21 Johnson Controls NOTES...
Page 22: ...JOHNSON CONTROLS 22 FORM 145 14 IOM1 908 NOTES...