MODEL
VOLTAGE
COMPRESSOR
EVAPORATOR
MIN. CCT.
MAX FUSE /
#
QTY
RLA
LRA
HP
FLA
RPM
AMPACITY
CCT. BKR. AMP
060A
208-230/3/60
1
@ 19.3
123.0 1.00
3.1
1800
27.23
45
460/3/60
1
@
7.5
49.5
1.00
1.6
1800
10.98
15
575/3/60
1
@
6.4
40.0
1.00
1.3
1800
9.30
15
096A
208-230/3/60
2
@ 13.9
88.0
1.50
4.4
1800
35.68
45
460/3/60
2
@
7.1
44.0
1.50
2.2
1800
18.18
25
575/3/60
2
@
5.4
34.0
1.50
1.8
1800
13.95
15
120A
208-230/3/60
2
@ 19.3
123.0 2.00
6.0
1800
49.43
60
460/3/60
2
@
7.5
49.5
2.00
3.0
1800
19.88
25
575/3/60
2
@
6.4
40.0
2.00
2.4
1800
16.80
20
OVERSIZE EVAPORATOR MOTORS
MODEL
VOLTAGE
COMPRESSOR
EVAPORATOR
MIN. CCT.
MAX FUSE /
#
QTY
RLA
LRA
HP
FLA
RPM
AMPACITY
CCT. BKR. AMP
096A
208-230/3/60
2
@ 13.9
88.0
2.00
6.0
1800
37.28
50
460/3/60
2
@
7.1
44.0
2.00
3.0
1800
18.98
25
575/3/60
2
@
5.4
34.0
2.00
2.4
1800
14.55
15
120A
208-230/3/60
2
@ 19.3
123.0 3.00
8.4
1800
51.83
70
460/3/60
2
@
7.5
49.5
3.00
4.2
1800
21.08
25
575/3/60
2
@
6.4
40.0
3.00
3.4
1800
17.80
20
SUPPLY AIR BLOWER PERFORMANCE
EXTERNAL STATIC PRESSURE - Inches W.C.
MODEL
SUPPLY
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
#
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800
846 0.41 936 0.48 1024 0.56 1107 0.64 1195 0.74 1259 0.82 1325 0.90 1400 0.99
-
-
060A
2000
917 0.54 999 0.62 1079 0.71 1157 0.79 1233 0.89 1305 0.98
-
-
-
-
-
-
2200
994 0.70 1069 0.79 1142 0.88 1214 0.98
-
-
-
-
-
-
-
-
-
-
3000
810 0.65 900 0.78 986 0.91 1066 1.04 1143 1.17 1221 1.32 1294 1.48 1363 1.63 1433 1.79
096A
3200
851 0.78 938 0.91 1018 1.04 1095 1.18 1170 1.32 1236 1.42 1305 1.56 1380 1.74 1447 1.90
3400
892 0.91 974 1.05 1051 1.19 1125 1.33 1196 1.48 1266 1.64 1320 1.81 1390 1.90
-
-
3600
927 1.05 1006 1.20 1081 1.34 1152 1.50 1220 1.65 1287 1.81 1353 1.98 1405 2.07 1472 2.17
120A
4000
1012 1.40 1085 1.56 1153 1.73 1220 1.89 1283 2.06 1345 2.23 1405 2.41 1464 2.59 1522 2.78
4400
1100 1.83 1166 2.00 1230 2.18 1292 2.37 1351 2.55 1410 2.74 1466 2.92
-
-
-
-
NOTE:
1. At higher evaporator airflows, and wet bulb conditions condensate carry-over may occur. Adjust airflow downward as necessary.
2. Values include pressure drop from wet coil and clean filters.
3. Shaded areas indicate oversize motors
NOTES:
Data shown for packaged unit installation, with single point power supply.
Min. Circuit Ampacity (MCA) = 1.25 x Largest single motor Amps (FLA or RLA) + sum of the remaining motor Amps
Max Fuse/Cct. Bkr Size (MFS) = 2.25 x Largest motor Amps + sum of the remaining motor amps
Select next smallest NEC listed fuse from calculated value
STANDARD EVAPORATOR MOTORS
Summary of Contents for CPH 060
Page 7: ...FORM 145 14 IOM1 908 7 Johnson Controls TYPICAL INSTALLATION LAYOUT CPH060 SHOWN LD13464...
Page 10: ...JOHNSON CONTROLS 10 FORM 145 14 IOM1 908 060 LD13465...
Page 11: ...FORM 145 14 IOM1 908 11 Johnson Controls 096 120 LD13466...
Page 18: ...JOHNSON CONTROLS 18 FORM 145 14 IOM1 908 TYPICAL SCHEMATIC...
Page 20: ...JOHNSON CONTROLS 20 FORM 145 14 IOM1 908 NOTES...
Page 21: ...FORM 145 14 IOM1 908 21 Johnson Controls NOTES...
Page 22: ...JOHNSON CONTROLS 22 FORM 145 14 IOM1 908 NOTES...