Sageon Shield Standalone Battery Monitor
PM990-4023-01, Issue 4
30
4. Finally, open a Telnet connection to port 9999, and press Enter within three seconds to go into Setup Mode. If
you wait longer than three seconds, the unit will reboot.
telnet 192.168.0.97 9999
5. Set all required parameters
Note:
The IP address you just set is temporary and will revert to the default value when the unit 's power is reset
unless you log into the unit and store the changes permanently. Refer to the chapter on configuration for
instructions on permanently configuring the IP address.
Lantronix, Inc, 2002, all rights reserved, used herein by permission from Lantronix.
7.2.3.
Configuring the Unit
The following section is excerpted from Lantronix "Embedded Integration Kit" Revision D 06/03/02, Part
Number 900-226.
You must configure the Lantronix Interface so that it can communicate on a network with Sageon CSU and
communicate with the Sageon CSU unit via the internal serial port.
The unit’s configuration is stored in nonvolatile memory (NVRAM) and is retained without power. You can
change the configuration at any time. The unit performs a reset after the configuration has been changed and
stored.
7.2.3.1.
Using a Telnet Connection
To configure the unit over the network, establish a Telnet connection to port 9999.
1. From the Windows Start menu, click
Run
and type the following command, where x.x.x.x is the IP address and
9999 is the unit’s fixed network configuration port number.
telnet x.x.x.x 9999 (Example: telnet 192.168.100.123 9999)
Note: Be sure to include a space between the IP address and 9999.
2. Click
OK
.
3. The Lantronix Universal Device Server window displays.
*** Lantronix Cobox Universal Device Server ***
Serial Number 1297-041 Software Version V03.9 (000211)
Press Enter to go into Setup Mode
4. To enter the Setup Mode, you must press Enter within 3 seconds.
*** basic parameters
Hardware: Ethernet Autodetect
IP addr 192.168.000.098, no gateway set
***************** Channel 1 *****************
Baudrate 09600, I/F Mode 4C, Flow 00
Port 10001