Sageon Shield Standalone Battery Monitor
PM990-4023-01, Issue 4
23
Click the Edit button next to Battery Parameters.
Set the Number of Battery Current Transducers that are in your system. The minimum is 1 the maximum is 4. I-
Bat FSD (A) is the full-scale rating of the current transducer.
Click the Edit button next to the Bat Mon checkbox.
Set the proper cell configuration for your system. Set the number of BCM batteries. This will be equal to the
number of Battery Strings that you have in your system. Set the high and low cell voltage thresholds and the cell
deviation from average thresholds from this screen.