Sageon Shield Standalone Battery Monitor
PM990-4023-01, Issue 4
22
In the top menu bar click SCU or from the main menu dropdowns click SCU > Display Parameters…
Set the Number of RECTs equal to zero. Set the desired alarm threshold levels for system voltage. EQ Enable
should be unchecked, EQ Per should be unchecked. Bat Disch Test, SMR Sleep Mode, AC1ph, and AC3ph
should be unchecked.
Click the Interface Parameters button, set the Interface type to Battery Distribution; leave Load FSD and Load
LVD unchecked.