Page 32
X100 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x100-5a
x100-man-Rev5a-0214.indd
12.5 Alarm Configuration
The
Alarm Configuration
page presents a matrix of tick boxes which are used to
programme how certain system conditions affect the actions of the alarm relays and
front panel LEDs. It is also used to define the ‘good’ condition (polarity) of the
auxiliary digital input. The screen shot below shows the factory default settings.
Figure 9 - Alarm Configuration WEB Page (typical)
12.5.1 Alarm Matrix Programming
K1 MAJ – An item ticked in this column will enable the MAJOR alarm relay
when active. Any item that is considered to represent a condition which
should be acted upon immediately should be ticked.
K2 MIN – An item checked in this column will enable the MINOR alarm
relay when active. Any item that is considered to represent a condition that
can wait for action at a later time should be ticked.
K3 & K4 – A ticked item in any of these columns will activate the relevant
auxiliary alarm relay.
Note that K5 – K8 are not installed in the X100 system.
MAJ LED – An item ticked in this column will enable the MAJOR alarm
LED when active.