TEMPERATURE COMPENSATION
Temp Comp (mV/°C/Cell) – Enter the temperature compensation slope value in
accordance with the specifications of the batteries that are being employed with the
system.
Number Of Cells – Enter the total number of battery cells.
Max Temp (°C) – Enter the maximum temperature at which temperature compensation
may be applied. Above this temperature the X100 will cease to apply further
compensation to the float voltage.
Min Temp (°C) – Enter the minimum temperature at which temperature compensation
may be applied. Below this temperature the X100 will cease to apply further
compensation to the float voltage.
VOLTAGE ALARMS
OVA – Enter the voltage above which the Over-Voltage Alarm will be triggered.
UVA – Enter the voltage below which the Under-Voltage Alarm will be triggered.
EVA – Enter the voltage below which the End-Voltage Alarm will be triggered.
TEMPERATURE ALARMS
Battery OT – Enter the temperature at which the battery Over-Temperature alarm
will be triggered.
External OT/UT – Enter the temperature at which the external Over-Temperature
and Under-Temperature alarms will be triggered.
Controller OT – Enter the temperature at which the controller’s internal Over-
Temperature alarm will be triggered. THIS SETTING SHOULD NOT NORMALLY
BE CHANGED.