Page 29
X100 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x100-5a
x100-man-Rev5a-0214.indd
SITE DETAILS
Site Name – Optional setting which may be used to identify the location of the unit.
Serial Number – Displays the unit serial number. (Cannot be changed.)
SYSTEM VOLTAGES
System – Dial in the Nominal system voltage; 12V, 24V or 48V.
Float – Enter the float voltage in accordance with the specifications of the batteries
that are being employed with the system.
Equalize – Enter the equalization voltage in accordance with the specifications of
the batteries that are being employed with the system.
Equ Time – Enter the desired time that the system should remain in equalize mode
in accordance with the specifications of the batteries that are being employed with
the system.
SYSTEM SHUNTS
Rect Shunt Amps – This is the 50mV Full-Scale rating for the internal shunt that
is used to measure the total rectifier current. THIS SETTING SHOULD NOT BE
CHANGED.
Load Shunt Amps – This is the 50mV Full-Scale rating for the shunt that is used to
measure the total load current. THIS SETTING SHOULD NOT BE CHANGED.
LVD SETTINGS
LVD1 Off – Enter the voltage at which the LVD1 contactor will open during a
battery discharge. The factory default setting is that recommended for most sealed
lead acid batteries.
LVD1 On – Enter the voltage at which the LVD1 contactor will re-connect once
the rectifiers are running. The factory default setting is that recommended for most
sealed lead acid batteries.
LVD2 Off & LVD2 On – These settings are not required for the X100.