A few seconds after the SELECT button has been pressed the X100 will respond
and the status and inventory information will be updated. ‘Live’ data is presented in
the form of 8 colored indicator blocks to the left. A green block indicates a ‘good’
condition and a red block indicates a ‘bad’ condition. In addition the unit’s internal
temperature is presented on the right.
Note that Sigma Series rectifiers include a single fan only and that two of the status
indicator blocks will always be grayed out.
‘Inventory’ data, presented on the right below the temperature measurement includes,
among other items, rectifier model number Serial Number and Revision Number.
12.2.1 Rectifier Inhibit (Shutdown)
The X100 includes a facility that enables the user to manually inhibit or
shutdown individual rectifiers. This may be desirable when a particular
rectifier is to be removed from the system for maintenance, although all
UNIPOWER rectifiers are Hot-Swap, or for some other reason.
To inhibit a rectifier first dial in the I²C address of the required unit and the
click on SHUTDOWN.
To restart a rectifier that has been inhibited dial in the I²C address of the
required unit and the click on RUN.
Note that any rectifiers which have been inhibited will remain in this state
until they are either restarted using the above method or the AC power is
recycled.