Table: 02 Prompts on LCD/OLED in Setting mode (Password=0002)
Sr.
No.
Display
prompts
Comment
1
Mute
XXX
To enable / disable the relay output.
XXX
can be
YES
or
NO
. Key K1 is used to
change it and K2 is used to confirm the
change and go to the next prompt.
2
ALM1 =
Xxxx
To set the ALM1 of the target gas. Key
K2 is used to increment the digit where
the cursor is positioned and key K1 is
used to shift the cursor to the next
(towards left) position. After the last
digit, blinking cursor disappears,
press K2 to accept changes and go to
the next prompt.
3
ALM2 =
xxxx
In a similar fashion the set ALM2 and
move to the next prompt.
4
Tx Id=
Xx
Not Available (only for KwikSense)
5
Mask =
xx
Factory set
6
Testing
LED-RLYs
To check (activate-deactivate) the LEDs
and Relays. During this prompt, if key
K1 is pressed, it activates all the
LEDs and corresponding relays one by
one. After that if key K2 is pressed,
it comes-out from the setting mode.
Note: if the alarm condition exists, the transmitter does not allow
the user to reset a latched Low or High alarm relay.