15 of 33
Settings:
The transmitter is calibrated & tested before shipping. Commonly
used parameter values are set at the factory.
Provision is made for the following settings on site
•
Mute
–
Yes/No
This provision is given to mute the hooter. During the
calibration mode or during the routine test of the
transmitter one can select “Mute” option to mute the hooter
i.e. to disable the Relay activation.
•
Alm1
–
(threshold Level Value)
This is Low alarm activation level.
•
Alm2
–
(
Short-term Threshold Level Value
)
This is High alarm activation level.
•
Mask
–
This is factory setting. Please do not change it without
consulting with the factory.
•
Relays/LED Test
This provision is given to test the Relays & alarm LED
operations site, when required.
To go into the parameter setting mode at any time, follow these
steps.
•
Touch the magnetic wand on the glass window at
the key “K2 “
•
The transmitter display prompts
for the “Password”.
(Setting Password = 0002)
•
Follow the below prompt for parameter setting.