Fault Alarm conditions & Advice:
In the event of a fault alarm condition, the fault alarm triggers
activating the connected field device. The transmitter indicates the
type of fault condition occurred.
Under the fault alarm condition, the fault alarm is activated.
Table: 06
Fault conditions
Fault
condition
4-20mA
Output
LED (Visual
Indicator)
LCD/OLED display
Sensor
self
test fail
At
start
–
up
sensor
self
test failed
2 mA
Visual
Indicator (LED)
turns to red
color
Numeric LCD/OLED
display indicates the
prompt “Error
-
No sensor “
Sensor Fault
2 mA
Visual
Indicator (LED)
turns to red
color
Numeric LCD/OLED
display indicates the
prompt
“Sensor –Fail “
Sensor Drift
2 mA
Visual
Indicator (LED)
turns to Red
color
Numeric LCD/OLED
display indicates the
prompt
“Sensor –
Drift”