PART III: OPERATION
36
11.0
AIR FLOW AND FUEL ADJUSTMENT
11.1 Adjustments - brief description
To change the burner setting during the testing in the plant, follow the next procedure.
Adjust the air and gas flow rates at the maximum output (“high flame”) first, by means of the air damper and the adjusting cam respec-
tively.
z
Check that the combustion parameters are in the suggested limits.
z
Check the flow rate measuring it on the fuel counter.
z
Then, adjust the combustion values corresponding to the points between maximum and minimum, according to the procedure
described on the “LMV5xx Service manual”.
z
Set, now, the low flame output (according to the procedure described on the “LMV5xx Service manual”) in order to avoid the low
flame output increasing too much or that the flues temperature gets too low to cause condensation in the chimney.
The heavy oil flow rate can be adjusted choosing a nozzle that suits the boiler/utilisation output and setting properly the delivery pres-
sure values.
Now adjust the pressure switches (see next par.).
11.2 User interface
The AZL2x.. display is shown below:
The keys functions are the following:
.ATTENTION:
During commissioning operations, do not let the burner operate with insufficient air flow (danger
of formation of carbon monoxide); if this should happen, make the fuel decrease slowly until the normal combu-
stion values are achieved.
IMPORTANT! the combustion air excess must be adjusted according to the values in the following chart.
Recommended combustion parameters
Fuel
Recommended (%) CO
2
Recommended (%) O
2
Heavy oil
11 ÷ 12.5
4.7 ÷ 6.7
Natural gas
9 ÷ 10
3 ÷ 4.8
Key F
Used to adjust the “fuel” actuator position (
F
uel): :
While pressing the
F
key, the “fuel” actuator position can be changed by means of the
+
and
-
keys.
Summary of Contents for KPBY70
Page 33: ...PART III OPERATION 33 FLUIDICS 12AG 90Kg h...
Page 53: ......
Page 54: ......
Page 55: ......
Page 57: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 64: ...8 Parameters level heating engineer...
Page 106: ...50 ERROR CODE TABLE...
Page 107: ...51...
Page 108: ...52...
Page 109: ...53...
Page 110: ...54...
Page 111: ...55...
Page 112: ...56...
Page 113: ...57...
Page 114: ...58...
Page 115: ...59...
Page 116: ...60...
Page 117: ...61...
Page 118: ...62...
Page 119: ...63...
Page 120: ...64...
Page 125: ......
Page 126: ......
Page 127: ......
Page 142: ......
Page 151: ......
Page 152: ......
Page 153: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 168: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 169: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 170: ...M12927CA MOUNTING 2...