5
Setting the kind of sensor to be connected to the device:
push
the
Enter
button: on the lower display (green)
Opr
appears. Using the
up and down arrows
find
ConF.
Push
Enter
to confirm.
Now on the green display the group
InP
appears. Push
Enter
and
InP1
is displaied. Enter to confirm.
You are inside
InP1
; the green display shows
Sen1 (sensor type)
, while the red display shows the chosen sensor
code
Push
Enter
to enter the
Sen1
parameter, then choose the desired sensor using the
arrows.
Push
Enter
to confirm
and
ESC
to escape.
Once selected the sensor, you can modify all the other parameters using
up and down arrows
according to the
tables here below.
ConF > InP >InP1
Parameter Value
Description
SEn1
type of sensor for
analog input 1
1
Pt100 3 fili
2
Pt100 2 fili
3
Pt1000 3 fili
4
Pt1000 2 fili
5
Ni1000 3 fili
6
Ni1000 2 fili
7
0 ÷ 135 ohm
15
0 ÷ 20mA
16
4 ÷ 20mA
17
0 ÷ 10V
18
0 ÷ 5V
19
1 ÷ 5V
OFF1
sensor offset
-1999..
0
.. +9999
Using the measured value correction (offset), a measured
value can be corrected to a certain degree, either up or down
SCL1
scale low level
-1999..
0
.. +9999
In the case of a measuring transducer with standard signal, the
physical signal is assigned a display value here
(for input ohm, mA, V)
SCH1
scale high level
-1999..
100
.. +9999
In the case of a measuring transducer with standard signal, the
physical signal is assigned a display value here
(for input ohm, mA, V)
dF1
digital filter
0…
0,6
…100
Is used to adapt the digital 2nd order input filter
(time in s; 0 s = filter off)
Unit
temperature unit
1
2
1 = degrees Celsius
2 = degrees Fahrenheit
(
bold
= factory settings)
Remark:
RWF50.2 e RWF50.3 cannot be connected to thermocouples.
If thermocouples have to be connected, convert the signal to a 4-20 mA one and set the RWF accordingly.
Summary of Contents for KPBY70
Page 33: ...PART III OPERATION 33 FLUIDICS 12AG 90Kg h...
Page 53: ......
Page 54: ......
Page 55: ......
Page 57: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 64: ...8 Parameters level heating engineer...
Page 106: ...50 ERROR CODE TABLE...
Page 107: ...51...
Page 108: ...52...
Page 109: ...53...
Page 110: ...54...
Page 111: ...55...
Page 112: ...56...
Page 113: ...57...
Page 114: ...58...
Page 115: ...59...
Page 116: ...60...
Page 117: ...61...
Page 118: ...62...
Page 119: ...63...
Page 120: ...64...
Page 125: ......
Page 126: ......
Page 127: ......
Page 142: ......
Page 151: ......
Page 152: ......
Page 153: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 168: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 169: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 170: ...M12927CA MOUNTING 2...